Download Print this page

Emerson COPELAND EAZYCOOL Replacement Manuallines page 2

Co2 refrigeration unit flashtank pressure transducer replacement
Hide thumbs Also See for COPELAND EAZYCOOL:

Advertisement

3
Disassembling the parts of the CO
Caution: Make sure that there is no pressure in affected unit parts!
1.
Disconnect the cable connector from the old pressure transducer and remove the PT5 from the port of the shut-
off valve. Use a 1/4" NPT plug (E) with sealing glue (Loctite) to blind the shut-off port.
Tighten the 1/4" NPT plug (E) to a tightening torque of 40 Nm.
2.
Remove the plastic plug from the metal partition wall.
3.
Remove the currently used plug on the Schraeder valve (SAE 1/4" on the shut off valve).
3
1
Figure 2
RGL_Unit_CO2_PT5/E/Rev00
unit
2
2
2/5