Technical Details - ABB UEMC 40 K6 Series Installation And Operating Manual

Motor operating device
Table of Contents

Advertisement

Available languages

Available languages

12.

Technical details

Weight
Operating time
Operating angle
Contactors power requirement
Shortest control pulse
Operating voltage range
Operating temperature range
Terminal block size
Motor
1) The operating angle can be redused by the
adjuster coupling (part of the adapter set)
Motor operating device
UEMC 40 K6_ - 24 VDC
- 48 VDC
- 60 VDC
- 110 VDC
- 125 VDC
- 220 VDC
For AC supplies, use rectifi ed motor current. Rated cur-
rent are the same as for a corresponding DC motor.
8 kg
opening 3,5 s
closing
3,5 s
110°
1)
3 W
0,1 s
0,85...1,1 x U
n
-40...+55 °C
2
6 mm
Rectifi ed DC, permanent magnet type
Rated current *)
Max. current **)
12 A
6 A
5 A
2 A
2 A
1 A
Protective mcb type
40 A
- STO S271 K8
20 A
- STO S272 K4
17 A
- STO S272 K4
5.5 A
- STO S272 K2
5.5 A
- STO S272 K2
3 A
- STO S282 UCK1
*) Rated current is the current under normal working conditions.
**) Max. current is the current for a stalled load from the motor ope-
rating device.
13

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents