Siemens FSD901-U2 Product Manual page 4

Floor repeater display

Advertisement

1. Insert the loop line and external power wire through the floor repeater display.
2. Mark the position for the 4 installation holes on flat wall (Fig. 2), drill the holes, put expansion bolts in and insert the
screws leaving a small gap for hanging the display.
3. Hang the floor repeater display over those screws through installation holes.
4. Open the front panel (Fig. 4/5), tighten the screws and make sure the display is fixed firmly.
5. Connect cables to terminals referring to the connection diagram (Fig. 3). Correctly set the internal 120Ω EOL
resistor referring to the section "EOL Resistor".
6. Close the front panel.
FSD connects to separate power supply, which needs to be UL Listed for Fire Safety Use and Power
Limited.
Dimension (mm)
Technical data
Details for ordering
Type
Material No.
FSD901-U2
S54433-C102-A4
FSD901-R2
S54433-C102-A3
FSD901-U3
S54433-C102-A1
FSD901-R3
S54433-C102-A2
Issued by
Siemens Industry, Inc.
Smart Infrastructure
8 Fernwood Road
Florham Park, NJ 08932
Tel. +1 973-593-2600
www.sbt.siemens.com/FIS
Doc No.
A6V10333726_c_en_--
Fig 4
Operating voltage
Operating current (quiescent)
Activation current
Operating temperature
Humidity
Communication protocol
Connection terminals
Color
Operating location
Part No.
100935670
101061934
101061935
100935673
100935693
Designation
Desigo system display (black)
Desigo system display (red)
Cerberus system display (bl)
Cerberus system display (red)
Technical specifications and availability subject to change without notice
Fig 5
24 VDC nominal / 19...28 VDC
60 mA
70 mA
0...+49 °C
≤93% rel.
UFP (RS485-BUS)
14-18 AWG
Black / Red
Indoor / dry
Weight
1.5 kg
1.5 kg
1.5 kg
1.5 kg
©
Siemens Industry, Inc., 2019
A5Q00041959