General Care; Annual Inspection Of Flues And Vents; Shutting Down The Omnitech; To Restart The Omnitech - Bradford White Brute OmniTech B H1250 Series User Manual

With touchscreen controls, onh/onv/occh/ocv cat i and cat iii, cat ii and cat iv

Advertisement

The

1.2 General Care

Your OmniTech will require very little
maintenance. However, as with any fine appliance
there are certain steps that should be taken to ensure
continuing optimum performance.
Keep the area around the OmniTech clean and
free from combustible materials, gasoline and other
flammable liquids and vapors.
The OmniTech must be completely isolated and
protected from any source of corrosive chemical fumes
such as trichlorethylene, perchlorethylene, chlorine,
etc.
Keep grille openings on the boiler free for proper
ventilation of interior components.
Do not obstruct or block a free flow of air to the
boiler to ensure proper ventilation.
If desired, clean the jacket surfaces with a
damp cloth and mild detergent. Do not use flammable
cleaning materials.
If sidewall vented, keep the vent terminal clear
of obstructions — do not pile snow against the vent
terminal. Clean the air filter(s) often, and then develop
an appropriate maintenance schedule.
1.3 Annual Inspection of Flue and Vents
Visually inspect the vent pipe and flue passages
once a year. Should any deterioration exist, have the
affected parts replaced by a qualified service person.

1.4 Shutting Down the OmniTech

1.
Switch off the main electrical disconnect switch.
2.
Close all manual gas valves.
3.
If freezing is anticipated, drain the OmniTech
and be sure to also protect the building piping
from freezing. This step to be performed by a
qualified service person.

1.5 To Restart the OmniTech

If drained, follow the Installation and
Operation Manual for proper filling and purging.
1.
Switch off the main electrical disconnect switch.
2.
Close all manual gas valves.
3.
WAIT FIVE (5) MINUTES.
4.
Set the aquastat or thermostat to its lowest
setting.
5.
Open all manual gas valves.
6.
Reset all safety switches (low water cut off,
manual reset high limit, etc.).
7.
Set the temperature controller to the desired
temperature setting and switch on electrical
power.
8.
Burner will go through a prepurge period and
ignitor warm-up period, followed by ignition.
User's Manual
1.6 In the Event of a Power Failure
The OmniTech can not be operated during an
electrical power outage. If there is an extended power
outage with danger from freezing, then the OmniTech
(and all other water systems) should be drained
completely. When draining the boiler, turn off main
electrical disconnect switch. When placing back in
service, refer to start-up instructions in the Installation
and Operation Manual for filling and purging. Draining
and filling shall only be done by a qualified service
person.
1.7 Full Service Every Three (3) Years
In addition to the annual visual inspections, a
qualified service agency should conduct a detailed
inspection of all flue product carrying areas of the
boiler and its venting system.
WARNING
Do not use this boiler if any part has been
under water. Immediately call a qualified service
technician to inspect the boiler and to replace any
part of the control system and any gas control which
has been under water.
WARNING
Should overheating occur or the gas supply fail to
shut off, do not turn off or disconnect the electrical
supply to the pump. Instead, shut off the gas supply
at a location external to the boiler.
FOR SERVICE
Contact your installing contractor, gas utility,
Bradford White dealer, or call Bradford White for the
nearest authorized representative in your area.