50FC-A06 SINGLE PHASE – MEDIUM STATIC — 3 TON VERTICAL SUPPLY (RPM - VDC)
CFM
0.2
RPM
Vdc
1500
1301
5.4
1625
1381
5.8
1750
1463
6.1
1875
1548
6.5
2000
1633
6.8
2125
1720
7.2
2250
1808
7.6
2375
1897
7.9
2500
1987
8.3
CFM
1.2
RPM
Vdc
1500
2053
8.6
1625
2101
8.8
1750
2152
9.0
1875
2206
9.2
2000
2262
9.5
2125
2320
9.7
2250
2380
10.0
2375
2500
Medium Static 1301-2390 RPM
APPENDIX C — FAN PERFORMANCE
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
0.4
RPM
Vdc
RPM
1476
6.2
1639
1545
6.5
1700
1615
6.8
1763
1688
7.1
1828
1764
7.4
1897
1842
7.7
1967
1922
8.0
2040
2003
8.4
2115
2086
8.7
2191
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.4
RPM
Vdc
RPM
2174
9.1
2289
2220
9.3
2332
2268
9.5
2378
2318
9.7
2372
9.9
68
0.6
0.8
Vdc
RPM
6.9
1788
7.1
1843
7.4
1901
7.6
1962
7.9
2025
8.2
2090
8.5
2157
8.8
2227
9.2
2298
1.6
1.8
Vdc
RPM
9.6
9.8
9.9
1.0
Vdc
RPM
Vdc
7.5
1925
8.1
7.7
1976
8.3
8.0
2031
8.5
8.2
2087
8.7
8.5
2146
9.0
8.7
2208
9.2
9.0
2271
9.5
9.3
2336
9.8
9.6
2.0
Vdc
RPM
Vdc