Side By Side Mounting - Omron Q2A Series Manual

Hide thumbs Also See for Q2A Series:
Table of Contents

Advertisement

Type
Terminal
Name
N.O. output
1NO
N.C. output
1NC
Digital output common
1CM
MFDO
2NO
(During Run)
2CM
MFDO
3NO
(Zero Speed)
3CM
MFDO
4NO
(Speed Agree 1)
4CM
Pulse train output
PO
(Output frequency)
MFAO1
A01
(Output frequency)
MFAO2
A02
(Output current)
Monitor common
A0V
E24V
External 24 V power supply input
External 24 V power supply ground
A0V
Communication input/output (+)
RS485+
Communication output (-)
RS485-
Shield ground
A0V
*1. Do not close the circuit between D24V and D0V terminals. Failure to obey will cause damage to the drive.
*2. Do not close the circuit between HC and D0V terminals. Failure to obey will cause damage to the drive.
*3. Do not set functions that frequently switch ON/OFF to MFDO because this will decrease the performance life of the relay contacts.
*4. Select DIP switch S2 to ON to enable the termination resistor in the last drive in a MEMOBUS/Modbus network.

Side by side mounting

16
50 mm
2 mm
30 mm
30 mm
Function (Signal level)
Relay output
30 VDC, 10 mA to 1 A
250 VAC, 10 mA to 1 A
Min. load: 5 V, 10 mA (Reference value)
Relay output
30 VDC, 10 mA to 1 A
250 VAC, 10 mA to 1 A
Min. load: 5 V, 10 mA (Reference value)
32 kHz max.
Select voltage or current output:
0 to 10 V / 0 to 100 %
-10 to 10 V / -100 to 100 %
4 to 20 mA
0 V
Supplies backup power to the drive control circuit, keypad and option board.
21.6 to 26.4 VDC, 700 mA
0 V
MEMOBUS/Modbus communication protocol
Use an RS-485 cable to connect the inverter
Maximum 115.2 kbps
0 V
120 mm
120 mm
50 mm
Frequency inverters

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents