Notes
Safety
National safety regulations
Failure to comply with national safety regulations may result in personal injury and
property damage.
●
●
●
●
Mounting position and ambient temperature
The devices can be snapped onto standard rails or screwed onto a flat surface.
Plug-in screw terminals connect power and interfaces.
Ambient temperature -5...50 °C (23...122 °F)
●
Wall, horizontal
–
–
Risk of overheating for failure to comply with ambient temperature
Burning and damage to the device
●
Ensure sufficient ventilation to comply with the permissible ambient temperature within
the panel or installation box. The temperature must be at least 10 K (18° F) lower
outside the installation box.
Disposal
Siemens Schweiz AG
Smart Infrastructure
CAUTION
Observe national provisions and comply with the appropriate safety regulations.
This equipment is intended only for use in a restricted access area (lockable cabinet)
This equipment is not suitable for use in locations where children are likely to be
present.
Conductors with a cross-section of 0.5 mm2 (AWG24) or greater shall comply with the
requirements of IEC 60332-1-2 and IEC 60332-1-3 or IEC TS 60695-11-21.
From left to right
From right to left
CAUTION
The device is considered an electronic device for disposal in accordance
with the European Guidelines and may not be disposed of as domestic
garbage.
●
Dispose of the device through channels provided for this purpose.
●
Comply with all local and currently applicable laws and regulations.
●
Dispose of empty batteries in designated collection points.
Ambient temperature -5...45 °C (23...113 °F)
●
Overhead
●
Wall, vertically
–
From top to bottom
–
From bottom to top
●
On a horizontal surface
5
A6V11646020_en--_b
2020-07-10