Mounting the anchor nut and
bolt
- Prepare 4 suspension bolts. (Each bolts
length should be same.)
- Measure and mark the position for the
Suspension bolts and the piping hole.
- Drill the hole for anchor nut on the ceiling.
- Insert the nuts and washer onto the
suspension bolts for locking the suspension
bolts on the ceiling.
- Mount the suspension bolts to the
anchornuts firmly.
- Secure the hangers onto the Suspension
bolts (adjust level roughly.) using nuts,
washers and spring washers.
- Adjust a level with a level gauge on the
direction of left-right, back-forth by adjusting
suspension bolts.
- Adjust a level on the direction of top-bottom
by adjusting suspension bolts. Then the unit
will be declined to the bottomside so as to
drain well.
Model (kBtu/h)
18 k/24 k
36 k/42 k/48 k/60 k
Suspension
Suspension
Suspension
(Unit : mm)
A
B
1 018
355
1 418
THE INDOOR UNIT INSTALLATION
Anchor nut
Ceiling
Nut
Washer
Washer
Washer
A
bolts
bolts
bolts
Suspension bol
Suspension bol
Suspension bol
Hangen
CAUTION
!
Installation information for declination
- Install declination of the indoor unit is
very important for the drain of the
convertible type air conditioner.
- Minimum thickness of the insulation
for the connecting pipe shall be 10
mm.
- If the Installation Plates are fixed to
horizontal line, the indoor unit after
installing will be declined to the
bottomside.
39
B
t
Suspension
bolts
Spring
washer
Nut
Max.
Washer
12 mm