SLC (Smart Load Control)
Function for set the variable target pressure which for the high
efficiency and comport operation depend on ODU load.
Mode setting method
Master unit PCB DIP switch on : No.5
Select the mode using '▶', '◀' Button :
"Func" Push the '●' button
Select the Function using '▶', '◀' Button :
"Fn14" Push the '●' button
Select the Option using '▶', '◀' Button :
"oFF","op1"~"op3" Push the '●' button
SLC(Smare Lode Control) Mode is set
SLC(Smare Lode Control) Mode
Setting
Mode
oFF
Not Setting
oP1
Smooth Mode
Slowly control, a target pressure value
oP2
Normal Mode
Normal control, a target pressure value
oP3
Peak Mode
Humidity Reference
Mode setting method
Master unit PCB DIP switch on : No.5
Select the mode using '▶', '◀' Button :
"Func" Push the '●' button
Select the Function using '▶', '◀' Button :
"Fn16" Push the '●' button
Select the Option using '▶', '◀' Button :
"oFF","on" Push the '●' button
Humidity Reference Control mode is set
Mode setting
- on:using humidity sensor
- oFF:not setting
<Using of humidity sensor>
- When used cooling operation of SLC function,it will improve energy
effcience because evaporation temperature wll be decreased
Detail of function
-
Fast control, a target pressure value
Central Control Connection at Indoor Unit side
Mode setting method
Master unit PCB DIP switch on : No.5
Select the mode using '▶', '◀' Button :
"Func" Push the '●' button
Select the Function using '▶', '◀' Button :
"Fn16" Push the '●' button
Select the Option using '▶', '◀' Button :
"Fn19" Push the '●' button
Select the Option using '▶', '◀' Button :
"on","oFF" Push the '●' button
Central Control Connection at Indoor
Unit side Mode is set
Compressor Input Current Limit
System Input Current Control
Mode setting method
Master unit PCB DIP switch on : No.5
Select the mode using '▶', '◀' Button :
"Func" Push the '●' button
Select the Function using '▶', '◀' Button :
"Fn20" Push the '●' button
Select the Option using '▶', '◀' Button :
"oFF","op1"~"op10" Push the '●' button
Compressor Input Current Limit mode is set
Compressor Input Current Limit
Mode
op1
op2
op3
op4
op5
op6
op7
op8
op9
op10
CAUTION
!
• Ask an authorized technician to setting a function.
• If do not use a function, set an off-mode.
• If use a function, capacity may go down.
Compressor Input Current Limit
95 %
90 %
85 %
80 %
75 %
70 %
65 %
60 %
55 %
50 %