LG Multi V 5 ARUV144DTE5 Installation Manual page 14

Cooling only
Hide thumbs Also See for Multi V 5 ARUV144DTE5:

Advertisement

14
Header Method
Ⓐ : Outdoor Unit
10 m or
Ⓑ : Header
less
Ⓒ : Indoor Units
Ⓓ : Sealed piping
Ⓔ : Connection branch pipe
between Outdoor
units : ARCNN41
Ⓕ : Connection branch pipe
between Outdoor
units : ARCNN31
Ⓖ : Connection branch pipe
between Outdoor
units : ARCNN21
Pipe Connection Method between outdoor
unit/indoor unit
Master
L2
L3
E
Indoor
Unit
1st branch
Refrigerant pipe diameter from outdoor unit to first branch
l 40 m (131 ft)
h 40 m (131 ft)
h See Table 2
A : Refrigerant pipe diameter from outdoor unit to first branch
E : Refrigerant pipe diameter for outdoor unit capacity
(Slave 1+ Slave 2+ Slave 3)
F : Refrigerant pipe diameter for outdoor unit capacity
(Slave 2+ Slave 3)
G : Refrigerant pipe diameter for outdoor unit capacity(Slave 3)
WARNING
!
• Branch pipe can not be used after header.
• It is recommended that difference in length of the pipes
connected to the indoor units (a~f) is minimized. Performance
difference between indoor units may occur.
Level Difference
(Outdoor unit ↔ Outdoor unit)
Max length from first branch to
each outdoor unit (L1, L2, L3)
(Table 1) Limit Pipe length
Longest
pipe
length(L)
Outdoor Unit
Max pipe
Equivalent
length
Indoor Unit
pipe length
Total pipe
length
Outdoor Unit
Difference in
Max
↔ Indoor Unit
height(H)
difference
Indoor Unit
Difference in
in height
↔ Indoor Unit
height(h)
Longest pipe
Pipe
length after
length(ℓ)
1st branch
h * : See Table 4
ODU Capacity
Slave3
Slave2
Master ≥ Slave 1 ≥Slave 2 ≥Slave 3
Slave1
Master
G
F
E
L 200 m [656 ft]
B
l 40 m [131 ft]
D
C
C
C
C
C
h 40 m (131 ft)
Slave1
Slave2
Slave3
H1
F
G
L1
5 m [16.4 ft]
Less than 10 m [32.8 ft]
(equivalent length of piping 13 m
[42.7 ft])
Combination of Y
Y branch
Header
branch/header
Method
Method
Method
A+B+C+D+e ≤ 150 m
A+B+b ≤ 150 m [492 ft]
A+C+e ≤ 150 m [492 ft]
A+f ≤ 200 m
[492 ft]
(200 m [656 ft] :
(200 m [656 ft] :
Conditional application)*
Conditional application)*
175 m [574 ft]
175 m [574 ft]
(225 m [738 ft] :
(225 m [738 ft] :
Conditional application)*
Conditional application)*
1000 m [3281 ft]
1000 m [3281 ft]
110 m [361 ft]
110 m [361 ft]
110 m [361 ft]
40 m [131 ft]
40 m [131 ft]
40 m [131 ft]
40 m [131 ft]
40 m [131 ft]
(90 m [295 ft] :
(90 m [295 ft] :
40 m [131 ft]
Conditional application)*
Conditional application)*
WARNING
!
Increased Pipe Diameter(table 2)
- When pipe length is 90 m [295 ft] or more from ODU to 1st
branch
- When level difference is 50 m [164 ft] or more
(Table 2) Refrigerant pipe diameter from outdoor unit to first branch. (A)
C
Pipe diameter when pipe
length is < 90 m (295 ft)
ODU
(Standard)
capacity
(hp)
Liquid Pipe
mm (inch)
8
Ø 9.52 (3/8) Ø 19.05 (3/4) Ø 12.7 (1/2) Ø 22.2 (7/8) Ø 12.7 (1/2) Not increased
10
Ø 9.52 (3/8) Ø 22.2 (7/8) Ø 12.7 (1/2) Ø 28.58 (1-1/8) Ø 12.7 (1/2) Not increased
12~16
Ø 12.7 (1/2) Ø 28.58 (1-1/8) Ø 15.88 (5/8) Ø 34.9 (1-3/8) Ø 15.88 (5/8) Not increased
18~22
Ø 15.88 (5/8) Ø 28.58 (1-1/8) Ø 19.05 (3/4) Ø 34.9 (1-3/8) Ø 19.05 (3/4) Not increased
24
Ø 15.88 (5/8) Ø 34.9 (1-3/8) Ø 19.05 (3/4) Ø 41.3 (1-5/8) Ø 19.05 (3/4) Not increased
26~34
Ø 19.05 (3/4) Ø 34.9 (1-3/8) Ø 22.2 (7/8) Ø 41.3 (1-5/8) Ø 22.2 (7/8) Not increased
36~60
Ø 19.05 (3/4) Ø 41.3 (1-5/8) Ø 22.2 (7/8) Ø 44.5 (1-3/4) Ø 22.2 (7/8) Not increased
62~64
Ø 22.2 (7/8) Ø 44.5 (1-3/4) Ø 25.4 (1) Ø 53.98 (2-1/8) Ø 25.4 (1) Not increased
66~96
Ø 22.2 (7/8) Ø 53.98 (2-1/8) Ø 25.4 (1) Ø 53.98 (2-1/8) Ø 25.4 (1) Not increased
(Table 3) Refrigerant pipe diameter from first branch to last branch (B,C,D)
Downward indoor unit
total capacity [kW(Btu/h)]
≤ 5.6(19 100)
< 16.0 (54 600)
≤ 22.4 (76 400)
< 33.6 (114 700)
< 50.4 (172 000)
< 67.2 (229 400)
< 72.8(248 500)
< 100.8(344 000)
< 173.6(592 500)
< 184.8(630 700)
≤ 224.0(764 400)
(Table 4) Conditional Application
• To satisfy below condition to make 40 m ~ 90 m of pipe length after first branch.
Condition
Diameter of pipes
between first branch and
the last branch should be
1
increased by one step,
except pipe diameter
B,C,D is same as
Diameter A
While calculating whole
refrigerant pipe length, pipe
2
B,C,D length should be
[656 ft]
calculated twice.
Length of pipe from each
225 m
3
indoor unit to the closest
[738 ft]
branch
1000 m
Length of pipe from
[3281 ft]
outdoor unit to the
farthest indoor unit 5
4
(A+B+C+D+e)] - [Length
of pipe outdoor unit to the
closest indoor unit 1
(A+a)] ≤ 40 m [131 ft]
Pipe diameter when pipe
differential (ODU↔IDU) is > 50 m
length is ≥ 90 m (295 ft)
Gas Pipe
Liquid Pipe
Gas Pipe
Liquid Pipe
mm (inch)
mm (inch)
mm (inch)
mm (inch)
Liquid pipe
[mm(inch)]
Ø 6.35(1/4)
Ø 9.52(3/8)
Ø 9.52(3/8)
Ø 9.52(3/8)
Ø 12.7(1/2)
Ø 15.88(5/8)
Ø 15.88(5/8)
Ø 19.05(3/4)
Ø 19.05(3/4)
Ø 22.2(7/8)
Ø 22.2(7/8)
Example
Ø 6.35(1/4) ' Ø 9.52(3/8), Ø 9.52(3/8) '
Ø 12.7(1/2), Ø 12.7(1/2) ' Ø 15.88(5/8),
40 m [131 ft] <
Ø 15.88(5/8) ' Ø 19.05(3/4), Ø 19.05(3/4) '
B+C+D+e
Ø22.2(7/8), Ø 22.2(7/8) ' Ø 25.4(1),
90 m [295 ft] ' B, C, D
Ø 25.4(1) ' Ø 28.58(1-1/8), Ø 28.58(1-1/8) '
Change a diameter
Ø 31.8(1-1/4), Ø 31.8(1-1/4) ' Ø 34.9(1-3/8),
Ø 34.9(1-3/8) ' Ø3 8.1(1-1/2)
A+Bx2+Cx2+Dx2
+a+b+c+d+e ≤
1 000 m [3 281 ft]
a,b,c,d,e ≤ 40 m
[131 ft]
(A+B+C+D+e)-
(A+a) ≤ 40 m
h 40 m [131 ft]
[131 ft]
Pipe diameter when height
(164 ft)
Gas Pipe
mm (inch)
Gas pipe
[mm(inch)]
Ø 12.7(1/2)
Ø 15.88(5/8)
Ø 19.05(3/4)
Ø 22.2(7/8)
Ø 28.58(1-1/8)
Ø 28.58(1-1/8)
Ø 34.9(1-3/8)
Ø 34.9(1-3/8)
Ø 41.3(1-5/8)
Ø 44.5(1-3/4)
Ø 53.98(2-1/8)
Indoor
Unit
L
l