SUN2000-(12KTL, 15KTL, 17KTL, 20KTL)-M0
User Manual
● If the external AC switch can perform earth leakage protection, the rated
● If multiple SUN2000s connect to the general residual current device (RCD)
● A knife switch cannot be used as an AC switch.
● The hex key is delivered with the inverter and bound to the hanging kit at the
Figure 5-4 Hex key
Procedure
Step 1 Connect the AC output power cable to the AC connector.
Figure 5-5 Stripping requirements
Issue 06 (2020-07-02)
NO TICE
leakage action current should be greater than or equal to 100 mA.
through their respective external AC switches, the rated leakage action current
of the general RCD should be greater than or equal to the number of
SUN2000s multiplied by 100 mA.
bottom of the inverter.
Copyright © Huawei Technologies Co., Ltd.
5 Electrical Connections
37