Application Range; Qualified Refrigerants And Oils; Application Limits; Ped Category And Maximum Allowable Pressure Ps - Emerson Copeland Scroll YH04K1E Application Manuallines

Compressors for heat pump applications
Table of Contents

Advertisement

2.4

Application range

2.4.1 Qualified refrigerants and oils

Compressors
Qualified
refrigerants
Copeland standard
oil
Servicing oil
Table 3: Qualified refrigerants and oil
Oil recharge values can be taken from Copeland™ brand products Select software available at
www.climate.emerson.com/en-gb.

2.4.2 Application limits

CAUTION
Inadequate lubrication! Compressor breakdown! The superheat at the
compressor suction inlet must always be sufficient to ensure that no refrigerant
droplets enter the compressor. For a typical evaporator-expansion valve
configuration a minimum stable superheat of at least 5 K is required.
For application envelopes and technical data, please refer to Copeland brand products Select
software available at www.climate.emerson.com/en-gb.

2.4.3 PED category and maximum allowable pressure PS

The YH*K1E compressor models covered in these guidelines are PED Class II, according to the
Pressure Equipment Directive PED 2014/68/EU.
The pressure PS is the maximum allowable pressure at the low- and high-pressure sides of the
compressor. The maximum pressure value PS for the individual compressor type is printed on the
nameplate of the compressor. Safety is established in compliance with the relevant standards
applicable to the given product.
Compressor
YH04K1E to
YH16K1E
Table 4: Maximum allowable pressures
4
YH04K1E to YH16K1E
R454C, R1234yf,
R513A, R134a, R407C
RL32 3MAF
RL32 3MAF
PS
High-pressure
Low-pressure
side
38 bar(g)
23.5 bar(g)
PS
TS
Low-pressure
side
side
50 °C
PED
PED
Class
Class
R513A
R454C
R134a
R1234yf
R407C
2
1
AGL_HP_ST_YHK1E_E_Rev02

Advertisement

Table of Contents
loading

Table of Contents