Zero Calibration; Span Calibration - WatchGas NEO Quick Start Manual

Photo-ionization detector
Hide thumbs Also See for NEO:
Table of Contents

Advertisement

Zero Calibration

Zero calibration sets the baseline for the sensor and is
done in normal fresh air or other clean air source.
To enter fresh air calibration:
Config Mode › Calibration › Zero Calib.
To start fresh air calibration:
Press the Right Key and a count-down timer
starts. When the count-down is finished, "Pass" or
"Fail" will be displayed. To abort the zero calibrati-
on use the Left Key during count down.

Span Calibration

Span calibration defines the response of the sensor to
the gas. It is done with a known concentration gas.
To enter span calibration:
Config Mode › Calibration › Span Calib
To start span calibration:
Apply Gas › Start Calibration ›Wait Count-down
Finish › Get Result.