PERFORMANCES
BGK = Gas fired rooftop
BDK = Dual fuel rooftop (heat pump + gas fired)
Table 5.14
050 GAS
100
Air flow
Kit
P
7200
K1
1*2.2
7800
K1
1*2.2
8400
K1
1*2.2
9000
K3
1*3.0
9600
K3
1*3.0
10200
K7
1*4.0
10800
K7
1*4.0
050 GAS
350
Air flow
Kit
P
7200
K4
1*3.0
7800
K4
1*3.0
8400
K7
1*4.0
9000
K6
1*4.0
9600
K8
1*5.5
10200
K8
1*5.5
10800
No kit
!
The pressure drop difference between Standard Heat and High Heat gas burners being negligeable,
these tables can be used for both.
P
Fan motor power in kW
150
RPM
Kit
P
RPM
760
K1
1*2.2
818
804
K1
1*2.2
859
850
K3
1*3.0
901
896
K3
1*3.0
944
943
K7
1*4.0
989
991
K7
1*4.0
1034
1039
K8
1*5.5
1080
400
RPM
Kit
P
RPM
1029
K4
1*3.0
1077
1058
K5
1*3.0
1105
1090
K6
1*4.0
1135
1124
K6
1*4.0
1167
1160
No kit
1198
No kit
No kit
evaporator fan
200
Kit
P
RPM
Kit
K1
1*2.2
874
K2
K2
1*2.2
911
K3
K3
1*3.0
950
K3
K3
1*3.0
991
K7
K7
1*4.0
1033
K7
K7
1*4.0
1076
K8
K8
1*5.5
1120
K8
450
Kit
P
RPM
Kit
K5
1*3.0
1124
K6
K6
1*4.0
1150
K6
K6
1*4.0
1178
No kit
No kit
No kit
No kit
Page 41 - Application Guide 04-2003 / Rooftop BALTIC Series - Page 41
250
300
P
RPM
Kit
P
1*2.2
927
K2
1*2.2
1*3.0
962
K4
1*3.0
1*3.0
998
K4
1*3.0
1*4.0
1037
K7
1*4.0
1*4.0
1076
K6
1*4.0
1*5.5
1117
K8
1*5.5
1*5.5
1160
K8
1*5.5
500
P
RPM
1*4.0
1169
1*4.0
1193
No kit
No kit
No kit
No kit
No kit
Highlighted value correspond to nominal conditions
RPM
979
1011
1045
1081
1119
1158
1198