The security codes A through F control the degree to which the operator may add/change/
delete the system parameters. Code A has the most privileges, code F has the least. For
detailed information concerning operator privilege levels, refer to the applicable ACU
manual.
Level Name
Password
Duress. Optional. A number (1-32) which instructs the SE 422 which action report to use
should a duress event occur. Default is 1.
System. Optional. A number (1-32) which instructs the SE 422 which action report to use
in response to system events in the SE 422. Default is 1.
Op. Override. Optional. A number (1-32) which instructs the SE 422 which action report
to use in response to operator overrides performed on the SE 422. Default is 1.
Alarm Delay. Optional. The amount of time in seconds (10-240) that an alarm condition is
allowed to exist before the alarm contact is closed. Default is 30.