Westinghouse SE 6000 Product Manual page 135

Westinghouse se 6000 security management system standard product manual
Table of Contents

Advertisement

S
6: S
A
ECTION
YSTEM
DMINISTRATION
Activate Code, Extension. Required. System code number for the type of action to be
performed. The extension applies to camera presets for pan and tilt, or image verification
when used with a Polaroid ID-4000 system. See table following this field description list.
Deactivate Code, Extension. Optional. If this task is to be automatically controlled by a time
coded event, enter the activate / deactivate code to be executed when the event time code
ends. See table following this field description list.
User Interactive. Conditional (applies to event times). A Y/N field to indicate if a timed task
can be cancelled by an operator.
A
/ D
C
CTIVATE
EACTIVATE
09
REQ MANUAL ACCESS
29
FORGIVE PASSBACK
41
MANUAL UNLOCK
45
MANUAL LOCK
46
TIME UNLOCK
56
BUILDING OPEN
57
BUILDING LIMITED
58
BUILDING CLOSED
70
DEACTIVATE OUTPUT
#
Activate / Deactivate Code
71
ACTIVATE OUTPUT
80
Chain Task
#
Activate/Deactivate Code
81
EXTENDED PROCESSING
89
SHUNT POINT
90
UNSHUNT POINT
91
REQUEST RESET DEVICE
92
REQUEST RESET KEYS
ODES
Request to perform manual access.
Request to forgive passback.
Unlock a sensor / lock for an unlimited time.
Lock a sensor /lock.
Unlock a sensor / lock for the amount of time specified by the
hardware settings, or, where applicable, by the amount of time in
the Unlock Time field of the reader entry screen.
Set building mode to OPEN
Set building mode to LIMITED
Set building mode to CLOSED
Turn off the specified output. Use this code if you are elsewhere
turning an output on for an unlimited time.
Explanation
Turn on a specified output for the amount of time shown in the Time
field on the point entry screen. If Time=0, the output will be on for
an unlimited amount of time, and you must turn it off with an a
deactivate output code.
Jumps to another group of task records and is used to consolidate
multiple task into a separate task.
Explanation
Instruct extended processing poller to process a transaction. Use
with elevator, parking control, VIP2, and poller transactions with a
point ID which matches the poller record for these functions.
Shunt a specified point.
Unshunt a specified point.
Perform a device reset for an applicable device.
Perform a key download for an applicable device.
6-11