Installation
Ceiling dimension and hanging bolt location
Installation of Unit
Install the unit above the ceiling correctly.
POSITION OF SUSPENSION BOLT
• Apply a joint-canvas between the unit and duct to absorb
unnecessary vibration.
• Apply a filter Accessory at air return hole.
Dimension
A
B
Capacity(kBtu/h)
L1
733 772 628 700 36 190 20 660 155 700
L2
933 972 628 700 36 190 20 860 155 900
L3
1133 1172 628 700 36 190 20 1060 155 1100
※ Install the unit leaning to a drainage hole
side as a figure for easy water drainage.
POSITION OF CONSOLE BOLT
• A place where the unit will be leveled and that can support
the weight of the unit.
• A place where the unit can withstand its vibration.
• A place where service can be easily performed.