Mpc-H Series - Back Panel; Mpc-H Series - Back Panel (Model Mpc-16H-1 Shown) - Western Telematic M User Manual

Mpc series managed power controllers
Table of Contents

Advertisement

1
3
BUS
A
BUS
B
2
6
Figure 2.2: MPC-H Series - Back Panel (Model MPC-16H-1 Shown)

2.2. MPC-H Series - Back Panel

As shown in Figure 2.2, the MPC-H Series Back Panel includes the following
components:
1.
Power Circuit A - Power Inlet: An IEC320-C20 AC inlet which supplies power to
MPC control functions and the Circuit "A" outlets. Also includes cable keeper
(not shown.)
Note: MPC-18H series units feature a single Power Inlet.
2.
Power Circuit B - Power Inlet: An IEC320-C20 AC inlet which supplies power to
MPC control functions and the Circuit "B" outlets. Also includes cable keeper
(not shown.) (Not present on MPC-18H series units.)
3.
Power Circuit A - Circuit Breaker(s): Note that on MPC-16H and MPC-18H
models, there are two circuit breakers for each power circuit. The circuit breakers
are rated as follows:
• MPC-8H-1, MPC-16H-1 and MPC-18H-1: 20 Amp Circuit Breaker(s).
• MPC-8H-2, MPC-16H-2 and MPC-18H-2: 16 Amp Circuit Breaker(s).
4.
Power Circuit A - Switched Outlets: AC Outlets that can be switched On, Off or
rebooted in response to user commands:
• MPC-8H-1: Four (4) each, NEMA 5-20R Outlets.
• MPC-8H-2: Four (4) each, IEC320-C13 Outlets.
• MPC-16H-1: Eight (8) each, NEMA 5-20R Outlets.
• MPC-16H-2: Eight (8) each, IEC320-C13 Outlets.
• MPC-18H-1: Eight (8) each, NEMA 5-20R Outlets.
• MPC-18H-2: Eight (8) each, IEC320-C13 Outlets.
4
A-1
A-2
A-3
A-4
B-1
B-2
B-3
B-4
5
2-3
BUS
A-5
A-6
A-7
A-8
BUS
B-5
B-6
B-7
B-8
6
Unit Description