2.8

Burner installation

1.
Separate the burner body and the fl ange.
2.
Remove the brake plate from the oil pipe.
3.
Install the selected nozzle. (See Technical data)
4.
Install the brake plate on the oil pipe
5.
Remove the burner tube from the fl ange.
6.
Install the fl ange with gasket on the boiler.
7.
Install the burner tube on the fl ange. Make sure that the hole in the
front of the burner tube pipe is pointing down. This allows any drops of
oil to fl ow out.
8.
Insulate between the burner and boiler door to reduce radiated heat.
9.
• Fit the burner body on the fl ange, B40 MF
• Slide the burner body on the guides, B45-2 MF
10.
Lock the burner body using with the nut/nuts.
11.
Connect the oil hoses to the pump, see paragraph 2.3
12.
Connect burner electrically, see paragraph 2.4
!
Because the burner tube must be installed from the inside the
boiler, it must be possible to open the boiler or have a hinged
fl ange that is designed so that it can be reconnected with the
burner tube installed.
2.9

Check oil line seals

Once the burner has been installed and commissioned, the seals of the
various coupling elements should be checked (A). These may, due to
temperature fl uctuations or transportation, start to leak.
Temperature fl uctuations arise from the process of heating oil used in these
burners.
When a leak is detected, it is usually suffi cient to tighten the coupling
element that is leaking.
A
A
For installers
Bentone B40 MF/B45-2 MF
21