178 129 53-3 CR00505 2025-05-19 Providing sustainable energy solutions worldwide Installation- and maintenance instruction B 40 MF LMO24.255C2E E4NC-1069 Translation of the original instructions.
Page 2
1~230V 1,0A 50Hz IP 20 Motor supply MADE IN SWEDEN BY 1. Manualer på övriga språk 1. Manuals in other languages 1. Manualer på andre sprog 2. www.bentone.com\ 2. www.bentone.com\ 2. www.bentone.com\ nedladdning download download eller scan QR- eller scanna QR-koden.
The electrical installation must be professionally carried out in • accordance with applicable high voltage regulations, as per Enertech’s recommendations. Before servicing, shut off the fuel supply and turn off the power to the • 165 105 60 Bentone...
Page 5
- fitting and installation work has been completed and approved - electrical installation has been correctly performed - flue gas ducts and combustion air ducts are not blocked - all actuators and control and safety devices are in working order and correctly set Bentone...
Page 6
Delivery check • Make sure everything is delivered and the goods have not been damaged during transit. If something is wrong with a delivery, report it to the supplier. • Transport damage must be reported to the shipping company. • Bentone...
DIN 51605:2010-10. and is used for: • Water heating generators. Hot air generators (these require LMO 24 255 C2E). • Dimensions B 40 MF Ø B Ø C B 40 MF * Min. recommended distance to floor. 165 205 77-2...
Working field B 40 MF 6.5-29.5 kg/h 65-300 kW mbar -1,0 Used lower calorific value of 10.00 kWh/kg for rapeseed oil in accordance with DIN 51605:2010-10 Electric Specification Type Motor Complete burner Sound 450W 230V 50/60Hz B 40 MF 230V 3,5A 400V 8,5A 50Hz 84 dBA ±...
Setting of brake plate and air flow *NB It is important that the spark does not strike against the brake plate or nozzle B 40 MF 2,5-3,0 6,5-7,0 Recommended nozzle and pressure Because of the various boiler types with varying furnace geometries and furnace loads, it is impossible to commit to a certain scattering angle or a specific distribution pattern.
This procedure ensures a good start after standstill. Altered structure of the oil can give rise to altered viscosity, pumpabilty and ignitability. This can cause the pump, valves and nozzles to get blocked Bentone...
63,08 748,18 10,00 63,04 747,63 65,84 780,87 68,53 812,76 71,12 843,44 11,00 70,75 839,1 73,9 876,41 76,91 912,2 79,82 946,63 12,00 The table applies to oil with a viscosity of 4.4 mm /s at a density of 830 kg/m Bentone...
The vacuum should not fall below 0 bar in the suction line during start-up. 3.3.1 Proposed pipe routing for oil distribution systems without transport pump This type of connection should be used only when the oil has a viscosity less than 30 mm²/s. Self-cleaning filter 165 205 78 Bentone...
Connect the Euro plugs. (See Electrical equipment) Make sure the burner operations switch (S1) is off. Turn on the main switch. If any electrical connection is used other than that recommended by Bentone, there may be a danger of damage to property and personal injury. Bentone...
See under Basic settings. Note that it is simply a matter of a basic setting that should be adjusted retrospectively once the burner has started. You should then conduct a flue gas analysis and soot quantity measurement. Bentone...
(A). These may, due to temperature fluctuations or transportation, start to leak. Temperature fluctuations arise from the process of heating oil used in these burners. When a leak is detected, it is usually sufficient to tighten the coupling element that is leaking. Bentone...
Function description B 40 MF 1-stage burner When the installation calls for heat, the burner's preheater starts to heat the oil. Once the oil reaches the set temperature, the burner receives the signal to start. Hot oil is flushed throughout the burner's oil system.
Basic settings Examples of basic setting B 40 MF Burner output 200 kW Estimated nozzle output 200 kW/10 kWh/kg*= 20 kg/h Nozzle selection in accordance with the table. (See technical data) Nozzle selection is based on the selected pump pressure and the desired effect.
The nozzle assembly control is manually adjusted (B) in order to achieve optimal pressure loss for good combustion. Air setting B 40 MF Set the operations switch (S1) on the on position (I). Loosen the screw (E) that locks the air adjustment knob. Adjust the position of the air damper using the wheel until the desired air flow is achieved.
Fit the Euro plugs and turn on the main current. burner tube installed. Check combustion. NB: When soiled, always replace nozzles with new nozzles. Do not clean. When servicing/replacing components that affect combustion, an analysis and soot test shall be carried out on the installation. 165 205 81 Bentone...
Adjust the air damper and its position. Fit the burner and the burner flange together and secure with the nut (G). Fit the Euro plugs and turn on the main current. Check combustion. When servicing/replacing components that affect combustion, an analysis and soot test shall be carried out on the installation. Bentone...
Use caution when operating the burner, surfaces may be hot. When servicing oil bearing components, check for oil leakage when the burner is commissioned after servicing. When servicing/replacing components that affect combustion, an analysis and soot test shall be carried out on the installation. Bentone...
Start the burner. Check combustion. Use caution when operating the burner, surfaces may be hot. When servicing oil bearing components, check the oil density when the burner is commissioned after servicing. When servicing/replacing components that affect combustion, an analysis and soot test shall be carried out on the installation. Bentone...
Fit the preheater hood using the screws (S). Fit the Euro plugs and turn on the main current. Start the burner. Check combustion. When servicing/replacing components that affect combustion, an analysis and soot test shall be carried out on the installation. Bentone...
Restore the burner to operating condition. Fit the Euro plugs and turn on the main current. Start the burner. Check combustion. Pressure piston (V) and O-ring (Z) should be replaced at least every 10 year. When servicing/replacing components that affect combustion, an analysis and soot test shall be carried out on the installation. Bentone...
Check the ignition electrodes (See Setting the ignition electrodes). affected o-rings must (see technical data) be replaced. Fit the burner and the burner flange together and secure with the nut (G). Fit the Euro plugs and turn on the main current. Check combustion. When servicing/replacing components that affect combustion, an analysis and soot test shall be carried out on the installation. Bentone...
Route the cable in the same track as the immersion heater to the pump. Plug the immersion heater electrically, see Wiring diagram. Fit the Euro plugs and turn on the main current. Check combustion. When servicing/replacing components that affect combustion, an analysis and soot test shall be carried out on the installation. Bentone...
Page 30
6.10.2 Installation of immersion heater, nozzle holder Break the main current and disconnect the Euro plugs from the burner. Work the fan housing in accordance with B 40 MF, (see figure). Install the immersion heater in its intended hole (B) on the nozzle holder.
Cleaning is done by turning a knob on the filter that scrapes the surface of the filter. Where a self-cleaning filter is installed, the reliability of the burner may be increased without having to perform a complete service of the filter. When servicing/replacing components that affect combustion, an analysis and soot test shall be carried out on the installation. Bentone...
If the burner stops during operation because the temperature in the preheater is too low, preheater function should be checked. Check, for example, safety thermostats, power to the immersion heater(s), function immersion heater(s), etc. 165 205 82 Bentone...
When using a new oil grade, check combustion and adjust the burner settings in order to achieve good combustion. When servicing/replacing components that affect combustion, an analysis and soot test shall be carried out on the installation. Bentone...
The pressure switch may be set to max. 3.5 bar, which is the highest pressure for which the oil pump is designed at the return side. Setting a higher pressure will damage the gaskets in the pump. Reset button Setting, Pressure switch 165 205 83 Bentone...
Change the oil pump oil filter in accordance with the following. • Close the oil valves Unscrew the cover on the pump. • Replace the oil filter. • Replace head gasket. • Mount the cover on the pump. • Open the oil valves. • 165 105 86-2 2022-05-17 Bentone...
Vacuum gauge port 5. Inlet Oil under pressure 1. Gear set By passed oil returned to tank, or to suction 2. By-pass hole 6. Pressure adjustment 7. To nozzle 3. Pressure gauge port 4. By-pass plug installed 8. Return Bentone...
If the reset button is instead kept pressed a second time for at least 3 seconds, you can, via an interface, obtain the corresponding information on a computer or flue gas analyser. To return to normal operation: Press the reset button for 1 second Bentone...
Preheater temperature too low Check preheater function New oil type Adjust the preheater‘s set operating temperature Check that the oil used has the physical parameters that the burner is rated for. If not, change the oil. 165 105 09-2 2021-01-21 Bentone...
Check that the oil used has the physical parameters that the burner is rated for. If not, change the oil. Temperature of the oil from the tank is too low, increase the temperature of oil from tank Clean the pump filter Bentone...
Change the oil or the pump‘s oil parameters Pump worn Replace the pump Pump run using impure oil that has worn the Replace pump and install self-cleaning pump out prematurely filter in the oil system Blocked pump filter Check, clean pump filter Bentone...
11. Log of flue gas analysis Owner Tel. no: Adresss Tel. no: Installation Boiler Type Make Power kW Bentone Burner Type Model Serial no. Fuel Step 1 Step 2 Step 3 Draught in fireplace Fan Press mbar Filter smoke number Flue gas temp.
Page 44
EU Declaration of conformity Bentone Oil Burners Type BF 1 ST 146 B 45 B 80 ST 108 B 55 ST 120 B 30 B 65 ST 133 B 40 B 70 This declaration of conformity is issued under the sole responsibility of the manufacturer. The object of the declaration...