4.4 Pump

The pump is a non-self-priming, single-stage Grundfos HSEF
standard pump with volute casing. It has an radial suction port
and a radial discharge port with ANSI B 16.5 compliant flanges.
For technical data see page 24 chapter 15.3.1 Permissible flange
forces and flange torques.
The impeller diameter can be reduced to customise the pump
performance to a certain duty point. This means that the actual
impeller diameter differs from the standard diameter stated in
sales catalogues, data sheets, etc. The actual impeller diameter
is stated on the pump nameplate.
The HSEF pump is equipped with a stuffing box seal.

4.5 Engine

The pumps are driven by a stationary 4-stroke diesel engine from
John Deere or Doosan which has been specially adjusted to the
pump drive requirements of Clarke UK Ltd.
The rated engine power is adapted to the power requirement of
the pumps. The adjustment is made via the engine speed and
consequently this must not be changed. See appendix page 27
and section 1. Dimensions and weights for relationship between
the diesel engines and the individual pumps. Depending on
performance, the engines have a turbocharger and, if necessary,
also a charge air cooler.
The fuel injection pump has been set from factory,
Caution
and the setting must not be changed.
The engine is cooled via a heat exchanger in the water-cooled
John Deere and Doosan engines. The coolant is led to the heat
exchanger via a pipe connected to the discharge port of the
pump.

5. Identification

5.1 Pump
5.1.1 Nameplate
The nameplate shows all important data of the pump. It is
attached to top of the pump.
13
2
CENTRIFUGAL FIRE PUMP
HORIZONTAL SPLIT - CASE
1
MODEL
STAGE
IMP.DIA
5
9
RATED CAPACITY
RATED PRESSURE
8
150% PRESSURE MAX. PRESSURE
Fig. 4
Nameplate of a HSEF pump with FM approval
Pos.
Description
1
Pump type and model
2
Number of stages
3
Actual impeller diameter [mm]
4
Serial number
5
Rated flow Q [l/min]
6
Rated head H [m]
7
Rated speed n [rpm]
8
Head at 150 % flow [m]
9
Maximum operating pressure [bar]
10
Maximum pump power [kW]
11
Maximum suction pressure [bar]
12
Manufacturer
13
Approval
6
3
4
6
SERIAL
7
10
RATED APM
11
MAX. POWER
MAX. SUCTION
12
PRESSURE

5.2 Pump set

5.2.1 Nameplate
The nameplate shows all important data of the pump set. It is
attached to the base frame.
FIRE FIGHTING SYSTEM
1
Description:
Product number:
2
Main supply:
4
Impeller diameter:
mm
5
3
Q:
m /h
H:
6
P
:
kW
n:
2
8
W:
Made in Germany - P1
Week(yy.ww):
11
13
Grundfos Pumpenfabrik GmbH Willy - Pelz - StraBe 1.5 23812 Wahlstedt GERMANY
Fig. 5
Nameplate of an FM pump set
Pos.
Description
1
Type designation
2
Product number
3
Serial number
4
Engine type
5
Impeller diameter [mm]
6
Rated flow rate Q [m
7
Head H [m]
8
Rated engine power P2 [kW]
-1
9
Rated speed n [min
10
Weight [kg]
11
Country of origin
12
Production date (year and week)
13
CE mark
14
Manufacturer
3
Serial number:
Barcode:
PN
m
min
-1
7
kg
9
10
12
14
3
/h]
]