10. Operation

Detailed operation instructions are described in the installation
and operating instructions for the controller.
Observe the safety instructions in section
8. Commissioning and its subsections, as well as in
Note
the installation and operating instructions for the
individual components.
See also installation and operating instructions for
Note
the controller and diesel engine.

10.1 Alarm indicators

The most important operating and alarm indications are shown
via indicator lights and/or the display of the controller.
See installation and operating instructions for the controller.
If the controller has outputs for connection to a building
management system, you can monitor the pump set remotely.
To remove any faults, see section 13. Fault finding.
The following four operating modes are possible:

10.2 Automatic operation

Once you have installed and commissioned the pump set
according to the instructions, no further operation is necessary.
The pump set works automatically and switches itself on as soon
as water is taken from the sprinkler system and the pressure
switch thus detects a pressure drop.
The pump set will not be shut down in case of
Note
disruptions.
You can stop the pump set manually via the controller.

10.3 Manual operation

You can also start and stop the pump set manually for a
functional test, for restarting or after service work.
Do not leave the pump room during manual
operation. Observe all operating and fault indications
Caution
as the pump set will not stop automatically in case of
fault (e.g. too high cooling water temperature or too
low oil pressure).

10.4 Emergency operation

This function is only available for pump sets with
Note
diesel engine.
If the diesel engine does not start up in automatic operation after
six start attempts, the automatic operation is blocked. You can
start the pump set manually via the controller.

10.5 Weekly test run

Test the function of the pump set during a test run. See the
standard applying to the pump set.
Do not leave the pump room during manual
operation. Observe all operating and fault indications
Caution
as the pump set will not stop automatically in case of
fault (e.g. too high cooling water temperature or too
low oil pressure).

11. Shutdown

This section applies to the complete pump set. See
also installation and operating instructions for the
Note
controller and diesel engine.
Shut down is only possible when the pump is not
Note
running. If the pump is running, stop it via the
controller.
1. Close the isolating valve on the discharge side.
2. Close the isolating valve on the suction side.
3. Switch off the power supply via the controller.
Additional procedure for pump set with diesel engine
1. Close the fuel valve on the fuel tank.
2. Disconnect the positive pole first and then the negative pole of
the batteries.
We recommend that you drain the fuel into a suitable container.

12. Maintenance

Warning
Maintenance must be carried out by authorised staff.
Warning
Personal protective equipment must be used when
carrying out commissioning, maintenance and test in
order to prevent risk of personal injury if other
measures cannot be taken.
Such equipment must comply with the requirements
specified by the main contractor or operator of the
operations room or the site in question.
Minimum requirements are well-fitting clothing,
protective gloves, hearing protection, safety goggles
and safety shoes.
Warning
Make sure that persons cannot accidentally come
into contact with hot surfaces, liquids or exhaust
pipes.
The operator is responsible for ensuring that all
maintenance, inspection and installation work is
performed by qualified staff according to local
regulations and the standard applying to the pump
Note
set. A regular maintenance plan will help avoid
expensive repairs and contribute to trouble-free,
reliable operation.
Warning
Before starting work on the pump set, make sure that
the pump set has been switched off and cannot be
accidentally switched on.
Observe local regulations, the standard applying to
Note
the pump set and the installation and operating
instructions of the individual components.
See also installation and operating instructions for
Note
the controller and diesel engine.
19

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents