Number of Sounders Per Loop
See figure 5.
The ZP755HAV-2 sounder can be powered directly
from the loop of a ZP5 or ZP3 panel. The table below,
read in conjunction with figure 5, gives the quantity of
detectors and sounders that can be connected to a 2
core screened loop of:
1000 metres cable size 1.5mm
1.
10 metres panel to devices
80 detectors and 20 sounders
100 detectors and 15 sounders
2.
100 metres panel to devices
80 detectors and 20 sounders
100 detectors and 15 sounders
3.
200 metres panel to devices
60 detectors and 20 sounders
100 detectors and 15 sounders
4.
300 metres panel to devices
40 detectors and 20 sounders
110 detectors and 15 sounders