Installation Sheet
Operating Modes
The ZP755HAV-2 sounder has 2 modes of operation,
which are selected using switch 7 on dipswitch SW2.
It may be operated as a dedicated sounder or with a
detector fitted. See Figure 3.
1.
Operation as a stand alone sounder
Own unique loop
Address
1.1
Navigate the following menu to tag the
sounders as SAB: ZP3 Panel Menu/Setup/
Sounders/SAB/Add SAB. The Planner program
can also be used.
1.2
To map an alert to evac function the first input
type must be a fast flash input. The sounder
will sound the alert tone in response to a fast
flash input. The sounder will sound the evac
tone when the input configured as steady is
triggered, overriding the alert tone.
Installation sheet
ZP755HAV-2
ZP755HAV-2 Addressable Omni-directional Sounder Beacon
Figure 3
Switch 7 = ON
Emulation
The ZP755HAV-2 can operate as a ZP755HAV-2 or
emulate a ZP754. See Figure 4.
1.
ZP755 mode
Set switch 6 (dipswitch SW2) to OFF. Provides
user selectable 2-tone operation and full
monitoring. Operates with ZP3 software 1.18 or
higher.
2.
ZP754 Emulation Mode
Set switch 6 (dipswitch SW2) to ON. Emulates
ZP754, provides 2 fixed tones. Use with ZP5
panels or ZP3 panels with legacy software.
Tone Settings
See Figure 4 – Operating Modes.
Two different tones can be programmed to operate
from the panel. In ZP755HAV-2 mode these tones are
selected using switches 1, 2 and 3 on the function
dipswitch SW2.
For mode selection, refer to Operating Modes.
NOTE: In the ZP panel I/O mapping menu, outputs
are programmed as "steady" or "flashing". The link to
the table on the right is as follows:
Tone A = Panel setting "fast flash/slow flash."
Tone B = Panel setting "steady."
Page 3
No.: 1780 iss 02
Figure 4
501-1780ZE-1-02
12/12/2005