(4) Dimensions for Installation

DOP-103WQ
o
o
Operation Temperature is 0
C to 50
C and Storage Temperature is -20
DOP-107WV
o
o
Operation Temperature is 0
C to 50
C and Storage Temperature is -20
DOP-110WS
o
o
Operation Temperature is 0
C to 50
C and Storage Temperature is -20

(5) Installation and Wiring

Installation Notes:
Improper installation will result in malfunction and greatly reduce the life of the HMI. Be sure to
follow the guidelines in this quick start when installing the HMI.
In order to ensure the HMI being well ventilated, make sure that the ventilation holes are not
obstructed and provide sufficient clearance for the HMI.
To protect the panel, be sure to install a waterproof gasket into HMI.
For use on a flat surface of a Type 4X "Indoor Use Only" enclosure or equivalent. If Enclosure with
lower type rating will cause de-rating.
The allowable thickness of the panel for mounting should be less than 5 mm.
Installation Method:
Step 1:
Put the waterproof gasket into HMI and then
insert the HMI into the panel cutout.
Step 3:
Tighten the screws with torque less than 0.5N-M /
0.7N-M to avoid damage to the plastic case.
DOP-107/DOP-110 Torque: 6.17 lb-inch (0.7N-M)
DOP-103 Torque: 4.41 lb-inch(0.5N-M)
o
o
C to +60
C
Recommended wiring is as follows:
Type
Wire Gauge (AWG)
Solid
24 ~ 12
Stranded
24 ~ 12
o
o
C to +60
C
Be sure to perform wiring by referring to the following figure (power supply connector), wiring must
be rated 75℃ min.

(6) Specifications

o
o
C to +60
C
Model
DOP-103WQ
4.3" TFT LCD
Display Type
(65535 colors)
Resolution
480 x 272 pixels
LCD
LED Back Light (less than
Module
10,000 hours half-life at
Backlight
o
25
Display Size
95.04 x 53.856 mm
Brightness
400 cd/m² (Typ.)
CPU
Step 2:
Place the fasteners into slots and tighten the
screws till reaching the panel cutouts.
Step 4:
For heat dissipation, please keep a minimum
clearance of 60 mm on the rear of the HMI.
Stripped length
Torque
7 ~ 8 mm
5 kg-cm (4.3 lb-in)
7 ~ 8 mm
5 kg-cm (4.3 lb-in)
DOP-107WV
DOP-110WS
7" TFT LCD
10.1" TFT LCD
(65535 colors)
(65535 colors)
800 x 480 pixels
1024 x 600 pixels
LED Back Light (less than
LED Back Light (less than
20,000 hours half-life at
30,000 hours half-life at 25
o
o
C)
(Note 1)
25
C)
(Note 1)
C)
(Note 1)
154.08 x 85.92 mm
225.52 x 128.10 mm
450 cd/m² (Typ.)
450 cd/m² (Typ.)
ARM Cortex-A8 (800MHz)
Model
DOP-103WQ
DOP-107WV
Flash ROM
256 Mbytes
RAM
512 Mbytes
4-wire resistive touch screen
Touch Screen
> 10,000,000 operated
Buzzer
Multi-Tone Frequency (2 K ~ 4 K Hz)/80 dB
Ethernet Interface
10/100 Mbps Auto sensing (with built-in isolated power circuit
1 USB Slave Ver 2.0
USB
1 USB Host Ver 2.0
SD
N/A
RS-232 (supports flow
COM1
RS-232 (supports flow control)
control) / RS-485
(Note 2)
)
Serial
Communication
COM2
RS-422 / RS-485
(Note 2)
RS-232 (supports flow control) / RS-485
Port
COM3
N/A
Function Keys
N/A
Perpetual Calendar
Built-in
Cooling Method
Natural cooling
CE / UL (Please use shielding Ethernet cable and the magnetic ring with filter of
Safety Approval
300 ohm/100 MHz)
Waterproof Level of
IP65(Not be evaluated by UL)/NEMA4/ Type 4X indoor use only
Panel Display
+24 V
(-15% ~ +15%) (with built-in isolated power supply unit)
DC
Operation Voltage
(Note2)
Supplied by Class 2 or SELV circuit (isolated from MAINS by double insulation)
Voltage Endurance
500 V
for 1 minute (between charging (DC24V terminal) and FG terminals)
AC
Power Consumption
(Note
(Note 3)
5.8W (Max)
8.4W (Max)
2)
Backup Battery
3V lithium battery CR2032 × 1
o
About 3 years or more at 25
C but subjects to the temperature and the conditions
Backup Battery Life
during usage.
o
Operation Temperature
0
C ~ 50
o
Storage Temperature
-20
C ~ +60
o
Operating Environment
10% ~ 90% RH [0 ~ 40
C], 10% ~ 55% RH [41 ~ 50
Vibration Resistance
Conforms to IEC61131-2; Continuous: 5 Hz ~ 8.3 Hz 3.5 mm, 8.3 Hz ~ 150 Hz 1 G
Shock Resistance
Conforms to IEC60068-2-27: 11 ms, 15 G Peak , X, Y, Z direction for 6 times
Dimension
137 x 103 x 37.1
196 x 136 x 39
(W) x (H) x (D) mm
Dimension for
Installation
118.8 x 92.8
186.8 x 126.8
(W) x (H) mm
Weight
Approx.280g
Approx. 560 g
Note:
1. The half-life of backlight is defined as original luminance being reduced by 50% when the maximum
driving current is supplied to HMI. The life of LED backlight shown here is an estimated value under 25
normal temperature and humidity conditions.
2. The withstand voltage of the isolated power circuit is 1500 V peak for 1 minute.
3. Power consumption of HMI is the power consumed when not connecting to any peripheral devices. To
ensure normal operation of HMI, the recommended power supply is: power consumption x 1.5 ~ 2.
4. Isolated power supply is recommended.
5. DOPSoft, the program editor for DOP-100 series products and user manuals can be downloaded at
our website. In addition, the content of this instruction sheet may be revised without prior notice.
Please consult our distributors or download the latest version at http://www.delta.com.tw/ia.
6. DOP-100 series can be used for industrial automation equipment. Please read through this manual
carefully and install the product according to the instructions to avoid danger.
DOP-110WS
(Note 2)
)
SD * 1
(Note 2)
)
(Note 2)
)
(Note 2)
RS-422 / RS-485
)
(Note 3)
(Note 3)
11W (Max)
o
C
o
C
o
C]; Pollution degree: 2
270 x 180.9 x 47.25
255 x 170
Approx. 1.1 Kgs
o
C