2
PARAMETER CODE (HEX)
<Common> : Area accessible regardless of inverter models (Note 3)
Paramet
er
Address
0x0000
0x0001
0x0002
0x0003
0x0005
0x0006
0x0007
0x0008
0x0009
Parameter Name
Drive model
Drive capacity
Drive Input Voltage
S/W Version
Frequency
Reference
Run Command
Acceleration Time
Deceleration Time
Output Current
Unit
Read/Write
-
R
-
R
-
R
-
R
0.01Hz
R/W
-
R/W
0.1 sec
R/W
0.1 sec
R/W
0.1 A
R
9
Data Value (Hex)
4: SV-iS5
0: 0.75 1:1.5 2:2.2 3: 3.7
4: 5.5 5: 7.5 6: 11 7: 15 8:
18.5 9: 22 A: 30 B:37 C:45
D: 55 E: 75 F: 90 10: 110
11: 132 12: 160
13: 200
14:220 15:280 16:375 (Unit
: kW)
0: 220V 1: 440V
0100: Ver. 1.00,
0101: Ver 1.01
Bit 0: Stop
Bit 1: Forward Run
Bit 2: Reverse Run
Bit 3: Fault Reset
Bit 4: Emergency Stop
modbus-rtu iS5 manual.doc
Need help?
Do you have a question about the MODBUS-RTU and is the answer not in the manual?