3.2

Intended use

Fire-fighting of class A fires
Fire class B: Fighting fires involving non-polar liquids, e.g. petrol or
oil as well as polar liquids
Preventive foaming of fire-endangered materials
Only for use with synthetic multi-grade foaming agents
Only use the device in technically sound condition and in accordance
with the intended purpose and with safety and potential dangers in
mind.
3.3

Foreseeable misuse

Use of unsuitable foaming agents
Conversion or modification
Operation in technically unsound condition
Operation outside the approved characteristic values
Fitting of spare parts that are not approved or not suitable for the
operating conditions
3.4

Characteristic values

Flow rate at 5 bar
Foam coefficient
Effective foam throw distance S2 = 23 m M2 = 7 m S4 = 25 m M4 = 10 m
Optimum operating pressure
Max. operating pressure
Operating temperature
M1108B10 I Rev. 02-03/20
Adjustable foam nozzles S2/M2, S4/M4
S2/M2
200 l/min
S2 = 15
3 – 10 bar 3 – 5 bar
ENGLISH
S4/M4
400 l/min
M2 = 50
S4 = 15
3 – 10 bar 3 – 5 bar
16 bar (PN16)
- 20 °C to + 60 °C
DESCRIPTION
M4 = 50
27 / 40