Output 2 Wiring - Watlow 945 Series User Manual

1/4 din microprocessor-based auto-tuning control
Table of Contents

Advertisement

Output 1 & 2 Wiring
Figure 15 -
Process, 0 - 5VDC
Figure 16 -
Solid State Relay
Without Contact
Suppression
Figure 17 -
Solid State Relay
With Contact
Suppression
NOTE:
This output is supplied
with an arc suppression
snubber across the
output terminals. High
impedance loads may
remain energized even
though the output device
is turned OFF.
NOTE:
Minimum load resis-
tance is 500
. Available
current is 22mA
maximum. Typical
voltage drop across a
1K
load is 12 to 19
volts.
Figure 18 -
Switched DC Output
(Open Collector)
8
WATLOW Series 945 User's Manual
Output 1 - Process, 0 - 5VDC
H
945A - _
_ _ - _ 000
Load impedance: 10KΩ min.
Output 1 - Solid State Relay Without Contact Suppression
K
945A - _
_ _ - _ 000
Solid State Relay, Form A, 0.5 Amp
Off state impedance: 31MΩ max.
Output 2 - Solid State Relay With Contact Suppression
B
945A - _ _
_ - _ 000
Off state impedance: 20KΩ max.
Output 2 - Switched DC Output (Open Collector)
Switched DC, Open Collector,
C
945A - _ _
_ - _ 000
Non-Isolated
Load impedance: 10KΩ min.
17
+
+
-
18
-
17
N.O.
18
COM.
Suppression
14
N.O.
15
COM.
14
+
Logic
Switch
15
-
External
Load
External
Load
L2
L1
Fuse
Fuse
L1
L2
External
Load
External
Load
Install and Wire, Chapter 2