19.5 HUMIDITY TOO LOW! (EXPERT)

Feuchte zu niedrig!

19.6 SERVICE! (EXPERT)

Service!
KWL Hygrobox KWL HB.. EH/WW
35
• If the relative humidity falls below the reference value
by 20% for a period of 25 hours, the water is drained and
the unit switches off.
• Fault rectification only by the expert:
Check the inlet valve, motor, integrated humidity sensor
and osmosis membrane for proper function (osmosis
membrane blocked).
• The service message is set to an interval of 8600 opera-
ting hours by default.
• Fault rectification only by the expert:
The device should be serviced according to section 20.