Siemens RUGGEDCOM RX1501 Installation Manual page 65

Hide thumbs Also See for RUGGEDCOM RX1501:
Table of Contents

Advertisement

Certification
6.2 EMC and Environmental Type Tests
IEC 61000-4-29
IEC 60255-5
a
Siemens-specified severity levels
EMC Immunity Type Tests for IEEE 1613
Note
The RUGGEDCOM RX1501 meets Class 2 requirements for an all-fiber configuration
and Class 1 requirements for copper ports. Class 1 allows for temporary communica-
tion loss, while Class 2 requires error-free and interrupted communications.
Environmental Type Tests
56
Test
Voltage Dips
and Interrupts
Dielectric Strength
HV Impulse
Description
HV Impulse
Dielectric Strength
Fast Transient
Oscillatory
Radiated RFI
ESD
Test
IEC 60068-2-1
Cold Temperature
IEC 60068-2-2
Description
DC Power Ports
Signal ports
DC Power Ports
AC Power Ports
Signal ports
DC Power Ports
AC Power Ports
Signal ports
DC Power Ports
AC Power Ports
Signal ports
DC Power Ports
AC Power Ports
Signal ports
DC Power Ports
AC Power Ports
Earth ground ports
Signal ports
DC Power Ports
AC Power Ports
Enclosure ports
Enclosure Contact
Enclosure Air
Description
Test Ad
Dry Heat
Test Bd
Test Levels
30% for 0.1 s
60% for 0.1 s
100% for 0.05 s
2 kV (Failsafe Relay output)
1.5 kV
2 kV
5 kV (Failsafe Relay output)
5 kV
Test Levels
5 kV (Failsafe Relay Output)
5 kV
2 kV
1.5 kV
2 kV
± 4 kV @ 2.5 kHz
± 4 kV
2.5 kV common mode @1MHz
2.5 kV common
1 kV differential mode @ 1 MHz
35 V/m
± 8 kV
± 15 kV
Test Levels
-40 °C (-40 °F), 16 Hours
85 °C (185 °F), 16 Hours
RUGGEDCOM RX1501
Installation Manual, 05/2020, C79000-G8976-1054-17
Severity
Levels
 
 
Severity
Levels
 
 

Advertisement