Appendix A: Modbus Communication; Modbus Register - ABB Comem OLI Instruction Manual

Liquid level indicator
Table of Contents

Advertisement

TRANSFORMER COMPONENTS

Appendix A: MODBUS communication

A1
Register address
Operation for monitoring
0x2000
0x2001
0x2002
0x2003
0x2004
0x2005
0x2006
0x2007
0x200A
Data logging**
0x2100
0x2101
0x2102
0x2103
0x2104
0x2105
...
0x215C
0x215D
0x215E
0x215F
Events log
0x2300
0x2301
0x2302
0x2303
0x2304
...
0x248D
0x248E
0x248F
0x2490
*Date and time of an event are calculated in this way:
Event Date/Time = Timestamp Hi (seconds) + (216) x Timestamp Low (seconds) + (01-Jan-2014 00hh:00min:00sec)
** The daily maximum and minimum data were saved starting from the nearest day, in registers 0x2100 and 0x2101, at the farthest day, in registers
0x215E e0x215F.
Table 7

MODBUS register

Operation
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
...
R
R
R
R
R
R
R
R
R
...
R
R
R
R
Notes
Level value (0-100%)
Minutes from the last powering
Days from the last powering
Max level value (%) in the current day
Min level value (%) in the current day
Number of powering lost in the day
Minimum range value
Maximum range value
Software version
Max level in the day -1
Min level in the day -1
Max level in the day -2
Min level in the day -2
Max level in the day -3
Min level in the day -3
...
Max level in the day -23
Min level in the day -23
Max level in the day -24
Min level in the day -24
Events number
Timestamp Hi [Event 1]*
Timestamp Low [Event 1]*
Event type: value 4=Change Date[Event 1]
Level Value at the moment of the event [Event 1]
...
Timestamp Hi [Event 100]*
Timestamp Low [Event 100]*
Event type: value 4=Change Date[Event 100]
Level Value at the moment of the event [Event 100]