Ametek DR22X0 Series Installation And Operating Instructions Manual page 18

Radar level instrument for two-wire control systems
Table of Contents

Advertisement

DR22
0 Radar Level Instrument
X
Sequence for setting parameters (example) (for version with local display)
The following description refers to a storage tank with the parameter examples taken from
the illustration in this Section. If the device no longer contains the default parameters, the
keystroke combination for entering the numerical values may differ.
Activity
Entry into configuration menu
Setting the parameter: tank height
Display of default value
Input of tank height "5.30 m"
Confirm tank height and move to block
distance
Display default value
Enter block distance "0.60 m"
Confirm block distance and move to current
output configuration
Move to lower range value
Display default value
Enter lower range value (0.4 m = 4 mA)
Confirm lower range value and move to full-
scale range value
Display of default value
Enter full-scale value (4.0 m = 20 mA)
Confirm full-scale value and move to empty
tank spectrum
Select: re-record empty spectrum
Store changed parameters
Confirm and select: averaging
Confirm and start recording; then wait for
approx. 1-3 minutes!
Confirm and move to tank type
Display of default value
Select tank type "storage tank"
Return to measurement function with
confirmation of changed parameters
Keys to be
Content of DR22X0
actuated
display after activity
Fct. 1.0
OPERATION
↑ ↑ → →
Fct. 3.1.1
TANKHEIGHT
10.000 m
→↓ → 5x- →
05.300 m
3x-
↵ ↑
Fct. 3.1.2
BLOCKDIST
0.5000 m
→ ↑
0.6000 m
↵ ↵ ↑ ↑
Fct. 3.3
SIGNAL OUT
→ ↑ ↑
Fct. 3.3.3
SCALE 4 mA
+ 00.000 m
3x → 4x-
+ 00.400 m
↵ ↑
Fct. 3.3.4
SCALE 20mA
010.00 m
2x→ ↓ → 4x↑
004.00 m
↵ ↵ ↑ ↑ → ↑
Fct. 3.5.2
EMPTY.SPEC.
→ ↑ ↑
RECORD
ACCEPT. YES
↵ ↑
AVERAGE
↵ ↵
↵ 7x↑
Fct. 3.5.9
TANK TYPE
PROC TANK
↑ ↑
STORAGE T.
PARAM.CHECK,
5x↵
then START,
then meas.val. display
14
READY