Ametek DR22X0 Series Installation And Operating Instructions Manual page 13

Radar level instrument for two-wire control systems
Table of Contents

Advertisement

DR22
0 Radar Level Instrument
X
Configuration menu (version 7.00) (cont.)
Function (Fct.)
3.1.7
3.1.8
3.2
3.2.1
3.2.2
3.2.3
3.2.4
3.2.5
3.3
3.3.1
3.3.2
3.3.3
3.3.4
3.3.5
3.3.6
3.3.7
3.4
3.4.1
3.4.2
Input range
REF.OFFSET
Enter -10.00...0...+10.00 [m] Reference offset is added
TB.OFFSET
Enter-100.00...0...+100.00 [m] Tank bottom offset is added
DISPLAY
FCT.DISP
Select
UNIT.LENGTH
Select
PERCENT/BARGRAPH
UNIT.CONV.
Select
m3/l(Liter)/US Gal/
GB Gal/Ft3/bbl/PERCENT/
BARGRAPH/USER UNIT
USER UNIT
Text entry
ERROR MSG.
Select
SIGNAL OUT
FUNCTION I
Select OFF/LEVEL /DISTANCE/
CONVERSION/SW.OUTP.
RANGE I
Select
SCALE 4mA
Enter -200.00 ... +200.00 [m]
0.00 ... 99999.99 [m
SCALE 20mA
Enter -200.00 ... +200.00 [m]
0.00 ... 99999.99 [m
BAUDRATE
Select
ADDRESS
Enter
PROTOCOL
Select
USER DATA
LANGUAGE
Select
GB-USA/D/F/I/E/P/S Select language for the
ENTRY CODE 1
Select
Description
(compensates different
wave speeds in still wells)
to measured distance
values.
to measured level values.
LEVEL
Select function of display
(value to be displayed).
DISTANCE
CONVERSION
See also explanatory notes.
m/cm/mm/
Select unit for length value
inch/Ft/
to be displayed (only for
level and distance).
Select unit for conversion
value to be displayed
("volume table").
(see explanatory notes)
Enter user-defined unit for
10 characters
the conversion table.
NO/YES Select whether error
messages to be shown in
display.
Select function of the
current output.
4-20mA
Select range/error status
4-20mA/E3.6
for the current output (hold
4-20mA/E22
last value or 3.6 mA/22mA
in error status)
Enter lower measuring
3
]
range value for the current
output (4 mA).
(see explanatory notes)
Enter full-scale range value
3
]
for the current output (20
mA).
(see explanatory notes)
1200 Bd
Baud rate for HART®
communication (do not
change!).
0 ... 255 Enter device address.
(for HART® multidrop)
Select communications
HART
protocol
optional display.
NO/YES
Switch the access lockout
on/off.
9