Ametek DR22X0 Series Installation And Operating Instructions Manual page 12

Radar level instrument for two-wire control systems
Table of Contents

Advertisement

DR22
0 Radar Level Instrument
X
Description of functions
The tables on the following pages provide an overview of the parameters that can be set in
the configuration menu. This is followed by more precise explanations of some functions
and a typical configuration.
Configuration menu (version 7.00)
Function ( Fct.)
1.0
OPERATION
1.1
DISPLAY
1.1.1
FCT.DISP
1.1.2
UNIT.LENGTH
1.1.3
UNIT.CONV.
2.0
TEST
2.1
HARDWARE
2.1.1
MASTER
2.1.2
DISPLAY
2.1.3
STATUS
2.2
CUR.OUTP.I
2.2.1
VALUE I
2.2.2
TEST I
2.4
FIRMWARE
2.4.1
MASTER
3.0
INSTALL.
3.1
BASIS.PARAM
3.1.1
TANKHEIGHT
3.1.2
BLOCKDIST
3.1.3
ANTENNA
3.1.4
ANT.EXTENS.
3.1.5
DIST.PIECE
3.1.6
STILLWELL
Input range
Value display
Select 3.6 mA/4 mA/6 mA/...
... 20 mA/22 mA
Display
Select unit
m/cm/mm/
inch/Ft
Enter
0.50 ... 20.00 [m]
Enter
0.10 [m] ... tank height
Select
STANDARD
WAVE-STICK
Enter 0.00 [m] ... tank height
Enter 0 ... 2000 [mm]
Select
NO / YES
If Yes: enter 25... 200 [mm]
8
Description
identical with 3.2.1
identical with 3.2.2
identical with 3.2.3
Master hardware test.
Display hardware test.
Status information for Service
Display of actual value of the
current output.
Output of selected value to
the current output. With
safety query.
Display of master firmware
version.
Enter tank height (see
explanatory notes).
The unit entered here is also
used for all other length
entries.
Enter block distance = non-
measurable range below
bottom edge of flange (see
explanatory notes).
Select antenna type. WAVE-
STICK for all Wave-Stick
versions, except type "SW"
for stillwells.
All other = STANDARD.
Enter length of antenna
extension (not for Wave-
Stick: set to= 0)
Enter length of distance
piece above flange (high
temp. version = 120 mm).
Selection: without or with
still well.
With still well: enter inside
diameter in [mm]