Parts List
Indoor Unit
The
following
items
are included
with
the indoor
unit:
Table
1 - Installation
Materials
Description
Qty
Usage
Baffle (size 18)
1
Required for fresh air intake
Mark hangers,
piping and wiring Ioca-
Template
1
tions
NOTE:
The grille and the User Interface
are not included
with
unit.
For User Interface,
a wireless
remote, wired
remote,
or a
Zone Manager
can be ordered.
Outdoor
Unit
The following
items are included
with the outdoor
unit:
BODY
METERED
FLOW
C00L[NG
38HDF018-036
Fig.
4 - 38HDF018-036
A09499
BODY
A09500
Fig.
5 - 38QRF018-036
Piston
Flare
Model
Filter Drier
Pistons*
Cap
Connector
38HDF
_*
_*
_*
_*
38QRF
_*
_*
(qty 2)
_*
_* (qty 3)
Multiple pistons.
Quantity varies with size.
These instructions
cover the installation
and start-up
of the systems
listed in Table 2.
Table 2 - Matched
Systems
INDOOR UNIT
SYSTEM
SYSTEM
OUTDOOR
UNIT
MODEL NUM-
TYPE
SIZE
BER
018
38HDF018-3
40KMC018-3
Cooling
024
38HDF024-3
40KMC024-3
Only
030
38HDF030-3
40KMC03036-3
036
38HDF036-3/5/6
40KMC03036-3
018
38QRF018-3
40KMQ01824-3
024
38QRF024-3
40KMQ01824-3
Heat Pump
030
38QRF030-3
40KMQ03036-3
036
38QRF035-3/5/6
40KMQ03036-3
Cooling
018
38HDF018-3
40KMQ01824-3
with
024
38HDF024-3
40KMQ01824-3
Electric
030
38HDF030-3
40KMQ03036-3
Heat
036
38HDF036-3/5/6
40KMQ03036-3
SYSTEM
REQUIREMENTS
Clearances
Allow
sufficient
space
around
the indoor
and outdoor
unit
for
proper
airflow
circulation
and servicing.
Refer to Fig. 1 and Fig. 3
for minimum
required
clearances,
Piping:
Piping
and insulation
is field supplied,
PiDinu Lenuths
The
minimum
length
between
the indoor
and outdoor
units
is 10 fl
(3 m).
Refer
to table
3 for the maximum
lengths
allowed.
Table
3 - Maximum
Refrigerant
Line
Lengths
Unit
Max Line
Max Elevation
Max Elevation
Size
Length* ft(m)
(ID over OD) ft(m)
(OD over ID) ft (m)
18K
200 (61)
65 (19.8)
200 (61)
24K
200 (61)
65 (19.8)
200 (61)
30K
200 (61)
65 (19.8)
200 (61)
36K
200 (61)
65 (19.8)
200 (61)
Note:For
lengths greater than 25 ft (7.6 m), refer to the Duct Free Long
Line Guide.
Pipe
Sizes
Refer
to table
4 for pipe
sizes.
Table
4 - Pipe
Sizes
Pipe Sizes (in)
Unit Size
Mix Phase - in
Vapor - in
18K
3/8
5/8
24K
3/8
5/8
30K
3/8
3/4
36K
3/8
3/4
Note:Both
lines need to be insulated
using at least 1/2 inch closed foam
insulation.
Condensate
Drain Pipe Sizes
Refer
to table
5 for the required
sizes.
Table
5 - Drain
Pipe
Sizes
Unit Size
Inside
Diameter
- in
18K
1
24K
1
30K
1
36K
1