Figure 8:
Testing a trip contact
1 Trip contact under test
2 Current limiting resistor
To check the status of the output circuits driving the output relay via the
LHMI, select Main menu/Monitoring/I/O status/Binary output modules
and then navigate to the board with the actual binary output to be checked.
Test and change the relay state manually.
1.
To set the IED to test mode, select Main menu/Test/IED test mode/
TestMode and set the parameter to On.
2.
To operate or force the output relay to operate, select Main menu/Test/
Forcing/Binary output values and then navigate to the board with the
actual binary output relay to be operated/forced.
3.
Select the BOn_PO to be operated/forced and use
operate the actual output relay.
In PCM600, only the result of these operations can be checked by right-
clicking the product and selecting Signal Monitoring tool and then
A
V
Section 5
Troubleshooting
and
or
to
35