Troubleshooting - Mitsubishi Electric MR. SLIM PCA Series Service Manual

Split-type, heat pump air conditioners split-type, air conditioners
Hide thumbs Also See for MR. SLIM PCA Series:
Table of Contents

Advertisement

9

TROUBLESHOOTING

9-1. TROUBLESHOOTING
<Check code displayed by self-diagnosis and actions to be taken for service (summary)>
Present and past check codes are logged, and they can be displayed on the wired remote controller or controller board of out-
door unit. Actions to be taken for service, which depends on whether or not the trouble is reoccurring in the field, are summa-
rized in the table below. Check the contents below before investigating details.
Unit conditions at service
The trouble is reoccurring.
The trouble is not reoccurring.
OCH659A
Check code
Judge the problem and take a corrective action according
to "9-3. SELF-DIAGNOSIS ACTION TABLE".
Displayed
Conduct troubleshooting and ascertain the cause of the
trouble according to "9-4. TROUBLESHOOTING OF
PROBLEMS".
Not displayed
1Consider the temporary defects such as the work of
protection devices in the refrigerant circuit including
compressor, poor connection of wiring, noise, etc.
Re-check the symptom, and check the installation
environment, refrigerant amount, weather when the
Logged
trouble occurred, matters related to wiring, etc.
2Reset check code logs and restart the unit after finishing
service.
3There is no abnormality in electrical component,
controller board, remote controller, etc.
1Re-check the abnormal symptom.
2Conduct troubleshooting and ascertain the cause of the
trouble according to "9-4. TROUBLESHOOTING OF
PROBLEMS".
3Continue to operate unit for the time being if the cause
Not logged
is not ascertained.
4There is no abnormality concerning of parts such as
electrical component, controller board, remote controller,
etc.
25
Actions to be taken for service (summary)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents