NuAire BPS V-CO Series Installation Manual
NuAire BPS V-CO Series Installation Manual

NuAire BPS V-CO Series Installation Manual

Vertical boxer packaged solution with connect (co) control

Advertisement

Quick Links

1.0 SAFETY INFORMATION
The provision of the electrical supply and the connection of the unit to the mains must be
carried out by a qualified electrician.
Isolate from power supply before removing any covers. During installation / maintenance ensure
all covers are fitted before switching on the mains supply.
All-pole disconnection from the mains as shown in the wiring diagram must be incorporated
within the fixed wiring and shall have a minimum contact separation of 3mm in accordance with
latest edition of the wiring regulations.
This unit must be earthed.
Ducting must be securely fixed with screws to the spigot to prevent access to live parts. Duct
runs terminating close to the fan must be adequately protected by suitable guards.
If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or
similarly qualified persons in order to avoid a hazard.
Precautions must be taken to avoid the back-flow of gases into the room from the open flue of
gas or other fuel-burning appliances.
This appliance should not be used by children or persons with reduced physical, sensory or
mental capabilities or lack of experience and knowledge, unless they have been given supervision
or instruction concerning the safe use of the appliance by a person responsible for their safety.
Children shall not play with the appliance. Cleaning and user maintenance shall not be carried
out by children.
1.1 Symbols
GENERAL WARNING
Signifies a general warning regarding hazard specified by supplementary information.
ELECTRIC SHOCK
This unit must be completely electrically isolated before any panels are removed. Check
mains supply and control connections.
ROTATING PARTS
This unit contains fast moving rotational parts which may start automatically. It is the
sole responsibility of the installer to adequately guard these components.
REFER TO INSTRUCTION MANUAL
Read and understand the installation and maintenance manual before installing,
operating or maintaining this product.
Nuaire |
Western Industrial Estate
BPS V-CO
Vertical Boxer Packaged Solution
with Connect (CO) Control
Installation Manual
|
|
| nuaire.co.uk
Caerphilly
CF83 1NA
30. 07. 20. Document Number 671760
EMC Directive
2014/30/EU
LVD Directive
2014/35/EU
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the BPS V-CO Series and is the answer not in the manual?

Questions and answers

Summary of Contents for NuAire BPS V-CO Series

  • Page 1 REFER TO INSTRUCTION MANUAL Read and understand the installation and maintenance manual before installing, operating or maintaining this product. Nuaire | | nuaire.co.uk 30. 07. 20. Document Number 671760 Western Industrial Estate...
  • Page 2: Code Description

    Particulars of damage and/or incomplete delivery should be endorsed Nuaire would always recommend a site specific risk assessment by a by the driver delivering the goods before offloading by the purchaser.
  • Page 3 CENTRE SUPPORT CAN BE ON EITHER SIDE OF CENTRE LINE Section length Section length Section length 100.0 50.0 50.0 100.0 A (1:5) Overall unit length 50.0 50mm x 50mm Lifting hole Nuaire | | nuaire.co.uk 30. 07. 20. Document Number 671760 Western Industrial Estate Caerphilly CF83 1NA...
  • Page 4: Unit Storage

    •Left and right hand side M6 Upper 3 axis alignment clamps. If the storage period is to exceed two months, contact Nuaire for guidance on the appropriate ‘mothballing’ procedures. Do not stack Air leakage, air blow marks to the unit casings and unacceptable units, modules or components.
  • Page 5 4.8 Unit Connections 4.8.1 Ducting Nuaire do not provide ductwork connections with units, instead the open ended framework should be utilised. Flanged connections are available as an option, refer to technical documents for information relating specifically to the manufactured unit.
  • Page 6: Control Dampers

    If specified with order, spare sets of filters will be provided and should be stored in a clean, dry environment. Should you require spare filter media, please contact Nuaire. 4.10 Control Dampers Care should be taken to ensure that all spring return actuators have stopped running and completed their stroke.
  • Page 7 BPS size **. Weather Terminal & Damper, Right Handed, for Thermal Wheel Units. B**AT/RTD-L BPS size **. Weather Terminal & Damper, Left Handed, for Thermal Wheel Units. ** Insert one of the following for the relevant BPS unit. Nuaire | | nuaire.co.uk 30. 07. 20. Document Number 671760 Western Industrial Estate...
  • Page 8: Unit Access

    All keys are identical and will open any handle or hinge. The hinges do not need to be unlocked in normal operation of opening and closing. Nuaire | | nuaire.co.uk 30. 07. 20. Document Number 671760 Western Industrial Estate...
  • Page 9: Top View

    Top View of Access For Right Hand Thermal Wheel Units Top View Top View SUPPLY SUPPLY SUPPLY SUPPLY BYPASS CONTROLS CONTROLS 600mm 600mm Access Access Nuaire | | nuaire.co.uk 30. 07. 20. Document Number 671760 Western Industrial Estate Caerphilly CF83 1NA...
  • Page 10: Electrical Installation

    Cool Demand - The relay is powered when cooling is selected Switch Live 2 (SL2) terminal - A signal of 100-230V a.c. will activate the switch live 2 (Fan Boost) signal. Nuaire | | nuaire.co.uk 30. 07. 20. Document Number 671760...
  • Page 11: Connection Chart

    Cable glands are for additional ancillary cabling and are located on the sides of the units. Isolator Locations Cable Gland Locations Electric Heater Isolator Unit Isolator Nuaire | | nuaire.co.uk 30. 07. 20. Document Number 671760 Western Industrial Estate Caerphilly CF83 1NA...
  • Page 12 Unit onsite has code B822V/ER/AT-L. This indicates a size 22 unit with electric heating and Reverse Cycle DX cooling. Section 9.4 and 9.13 include the basic connection diagram and wiring diagram respectively. Nuaire | | nuaire.co.uk 30. 07. 20. Document Number 671760...
  • Page 13 24Vac LPHW Valve Supply (Constant) 24Vac CHW Valve Supply (Constant) 0-10V LPHW Valve Demand (10V = 100%) 0-10V CHW Valve Demand (10V = 100%) 0V COM 0V COM Nuaire | | nuaire.co.uk 30. 07. 20. Document Number 671760 Western Industrial Estate Caerphilly CF83 1NA...
  • Page 14 0-10V CHW Valve Demand (10V = 100%) adjustment knob inside the electric heater section. 0V COM T1 T2 T3 Electric Heater Section 1 Supply Required Nuaire | | nuaire.co.uk 30. 07. 20. Document Number 671760 Western Industrial Estate Caerphilly CF83 1NA...
  • Page 15 0-10V CHW Valve Demand (10V = 100%) adjustment knob inside the electric heater section. 0V COM T1 T2 T3 T1 T2 T3 Electric Heater Section 2 Supplies Required Nuaire | | nuaire.co.uk 30. 07. 20. Document Number 671760 Western Industrial Estate Caerphilly CF83 1NA...
  • Page 16 Connect space temperature sensor in place of extract temperature sensor for space temperature control. Valve not supplied as standard 24Vac LPHW Valve Open 24Vac LPHW Valve Close 0V COM Nuaire | | nuaire.co.uk 30. 07. 20. Document Number 671760 Western Industrial Estate Caerphilly CF83 1NA...
  • Page 17 Connect space temperature sensor in place of extract temperature sensor for space temperature control. Valve not supplied as standard 24Vac LPHW Valve Open 24Vac LPHW Valve Close 0V COM Nuaire | | nuaire.co.uk 30. 07. 20. Document Number 671760 Western Industrial Estate Caerphilly CF83 1NA...
  • Page 18 Connect space temperature sensor in place of extract temperature sensor for space temperature control. Valve not supplied as standard 24Vac LPHW Valve Open 24Vac LPHW Valve Close 0V COM Nuaire | | nuaire.co.uk 30. 07. 20. Document Number 671760 Western Industrial Estate Caerphilly CF83 1NA...
  • Page 19 The elctric heater air o temperature is set by an adjustment knob inside the electric heater section. T1 T2 T3 Electric Heater Section 1 Supply Required Nuaire | | nuaire.co.uk 30. 07. 20. Document Number 671760 Western Industrial Estate Caerphilly...
  • Page 20 The elctric heater air o temperature is set by an adjustment knob inside the electric heater section. T1 T2 T3 Electric Heater Section 1 Supply Required Nuaire | | nuaire.co.uk 30. 07. 20. Document Number 671760 Western Industrial Estate Caerphilly...
  • Page 21 The elctric heater air o temperature is set by an adjustment knob inside the electric heater section. T1 T2 T3 T1 T2 T3 Electric Heater Section 2 Supplies Required Nuaire | | nuaire.co.uk 30. 07. 20. Document Number 671760 Western Industrial Estate Caerphilly CF83 1NA...
  • Page 22: Operation

    The HX bypass damper opens on a 24 Vac signal which is produce PIR's. This is in addition to any software run-on times. from the bypass damper relay. Nuaire | | nuaire.co.uk 30. 07. 20. Document Number 671760 Western Industrial Estate...
  • Page 23 8.7 Fan Speed Control Input Once assigned to either input 4 or 5, the 0-10V input is scaled to 0-100% fan speed demand. Nuaire | | nuaire.co.uk 30. 07. 20. Document Number 671760 Western Industrial Estate Caerphilly...
  • Page 24: Room Temperature Control

    Air Temp. Air Temp. Air Temp. In room temperature control mode, the bypass damper is controlled according to the following chart. A minimum supply air temperature Nuaire | | nuaire.co.uk 30. 07. 20. Document Number 671760 Western Industrial Estate Caerphilly...
  • Page 25: Frost Protection

    The enable run-on time must be set to 3 minutes for reverse cycle units. This is required in order to keep the compressor running for at least 3 minutes for each period. Nuaire | | nuaire.co.uk 30. 07. 20. Document Number 671760...
  • Page 26: Bacnet Overview

    “Enable” MSV and boost the unit using the “Fan Boost” MSV. •Cooling Demand (Default Setting) This will provide a standard 0-10V cooling output. This output will only function if a cooling type is selected. Nuaire | | nuaire.co.uk 30. 07. 20. Document Number 671760 Western Industrial Estate...
  • Page 27 It is still at 7 because of priority 9. •Case 5 - Priority 9 is relinquished back to null. This allows priority 16 to take priority again and the present value becomes 0. Nuaire | | nuaire.co.uk 30. 07. 20. Document Number 671760...
  • Page 28 (e.g. MSTP & IP). This is possible because no matter the physical medium, BACnet messages are always the same. A router can be fitted to the network to translate BACnet between different physical media. Nuaire | | nuaire.co.uk 30. 07. 20. Document Number 671760 Western Industrial Estate...
  • Page 29 Puts the extract fan to setback speed 17769 (1)Off (2)On Extract Setback Speed The extract fan speed when Extract Setback 18258 Percent is enabled. Nuaire | | nuaire.co.uk 30. 07. 20. Document Number 671760 Western Industrial Estate Caerphilly CF83 1NA...
  • Page 30 Configurable output 4 (OUT4) 10173 Percent ESC BMS Thermic Chooses whether to demand thermal 17610 Auto (1)Auto (2)None (3)Heating Output output in 0-10v ESClassic BMS mode (4)Cooling Nuaire | | nuaire.co.uk 30. 07. 20. Document Number 671760 Western Industrial Estate Caerphilly CF83 1NA...
  • Page 31 The supply air temperature 10005 Degrees-Celsius Fresh Air Temp (H) The fresh air temperature 10008 Degrees-Celsius Extract Air Temp (C) The extract air temperature 10011 Degrees-Celsius Nuaire | | nuaire.co.uk 30. 07. 20. Document Number 671760 Western Industrial Estate Caerphilly CF83 1NA...
  • Page 32 Night Cooling Schedule 16014 Night C Sample Daytime schedule for winter or summer 15875 decision making Night C Sample Night Cooling Sample Schedule 16008 (1)Off (2)On Nuaire | | nuaire.co.uk 30. 07. 20. Document Number 671760 Western Industrial Estate Caerphilly CF83 1NA...
  • Page 33: Fire Alarm

    (1)Normal (2)Alarm Ala (Fire Alarm) For LCD Event Signal Only 17409 (1)Normal (2)Alarm Norm (Fire Alarm) For LCD Event Signal Only 17411 (1)Normal (2)Alarm Nuaire | | nuaire.co.uk 30. 07. 20. Document Number 671760 Western Industrial Estate Caerphilly CF83 1NA...
  • Page 34 (Sensor Actuator) SA Bus (Sensor Actuator) SA Bus For best results, use a linear network and switch on the EOL resistors at each end of the FC bus. Nuaire | | nuaire.co.uk 30. 07. 20. Document Number 671760 Western Industrial Estate...
  • Page 35 The BACnet IP to MS/TP Router exchanges information between networks and allows the controller to communicate on an IP network. One router is required for each MS/TP network. ESCO-IPN Nuaire | | nuaire.co.uk 30. 07. 20. Document Number 671760 Western Industrial Estate...
  • Page 36: Quick Setup

    Cancel – Quit and moves Network Settings the previous section Device Name FAD0351 TL-BRTRP-0 Device ID Home – Shortcut to the Nuaire BPS ESC 0909501 MAC Address configured Home Page Descriptions Field Advanced Display Nuaire BPS ESC 0909502 Baud Rate...
  • Page 37: Setting Favourites

    10050 password is set the home page will be locked. The only way to exit the target screen in this case is to press the Nuaire logo to the top right of the screen for 5 seconds. Setting Default Homepage...
  • Page 38: Setting Schedule

    The only way to exit the target screen in this case is to press the •Enable Nuaire logo to the top right of the screen for 5 seconds. A security password will then be requested to access the main menu. The •Time Schedule...
  • Page 39: Multiple Controllers

    This option can be changed via the Controller Wiring settings page. 12...24 VAC Alarm Log 12...24 VAC BACnet MS/TP Nor(A CIR 2) Nuaire BPS 09:47 16-10-15 Terminals Description Ala(A Cir 2) Nuaire BPS 09:44 16-10-15 Unused Power Supply (-) 12...24 VAC / VDC Power Supply (+) 12...24 VAC / VDC...
  • Page 40 It adjusts settings related to the Hour and Minute of the FAD integrated clock Day Of Week It adjusts settings related to the Day of Week (1-7) of the FAD integrated clock Nuaire | | nuaire.co.uk 30. 07. 20. Document Number 671760 Western Industrial Estate Caerphilly...
  • Page 41 Room Module Display Relative Humidity 10.1 Room Module Room Modules are electronic, wall-mountable sensors designed to work directly with the Nuaire control panel. Celsius Temperature Fahrenheit Temperature Room modules are automatically detected and require no set-up. The majority of RM modules monitor room temperature; however, options...
  • Page 42: Installation

    24VAC/DC supply must be provided in either case. SA+ SA- Bus Com 24 VAC/VDC Power Supply SA Power from Controller (15 VDC) Nuaire | | nuaire.co.uk 30. 07. 20. Document Number 671760 Western Industrial Estate Caerphilly CF83 1NA...
  • Page 43 200-203 Relative Humidity is not displayed ESCO-PL 80x120 200-203 Group 3 ESCO-CL 80x120 212-219 Powered Max of 4 via seperate 24vac/ Controller dc supply Nuaire | | nuaire.co.uk 30. 07. 20. Document Number 671760 Western Industrial Estate Caerphilly CF83 1NA...
  • Page 44 The shield must be earthed at the control panel end only and be made continuous along the bus length. Room Modules must not be fitted more than 150metres (cable length) from the controller. Nuaire | | nuaire.co.uk 30. 07. 20. Document Number 671760 Western Industrial Estate...
  • Page 45 Screwed Terminal SA Bus Screwed Terminal (Brown) Room Module Screwed Terminal Screwed Terminal Room Module Room Module Cable Type: Plain-eded shielded 2 twisted pair 22AWG Nuaire | | nuaire.co.uk 30. 07. 20. Document Number 671760 Western Industrial Estate Caerphilly CF83 1NA...
  • Page 46: Commissioning Checklist

    Wiring - Electric Frost Coil 07 - 22 applicable). •Thermal wheel belt tensioned. External •The correct installation procedure has been carried out in Rotary accordance to Nuaire’s recommendations. Isolator °C •Anti-vibration mounts are adjusted accordingly. •Rotate fan impellers and motors to ensure they run freely. Heater Temperature Setting •Check any additional bearings and couplings (where fitted...
  • Page 47: Maintenance

    Maintenance guidelines for all fans are down affected areas with a mild detergent solution and a soft brush. beyond this manual, please contact Nuaire for specific documents. Care should be taken not to damage the finned surface, and any cleaning fluids should be rinsed away with water.
  • Page 48: Electric Heaters

    80°C is detected. This action is performed independently of any controls fitted. Nuaire fitted controls will also stop heating if a fan or The product warranty applies to the UK mainland and in accordance heater failure is detected.
  • Page 49 The serial number will be found on the identification plate attached to the unit casing. Telephone 02920 858 400 aftersales@nuaire.co.uk Nuaire | | nuaire.co.uk 30. 07. 20. Document Number 671760 Western Industrial Estate Caerphilly...
  • Page 50 GENERAL In addition to the particular requirements given for the individual product, the following general requirements The equipment referred to in this Declaration of Incorporation is supplied by Nuaire to be assembled into should be noted. a ventilation system which may or may not include additional components. The entire system must be...
  • Page 51 Installation Manual BPS V-CO NOTES Nuaire | | nuaire.co.uk 30. 07. 20. Document Number 671760 Western Industrial Estate Caerphilly CF83 1NA...
  • Page 52 Installation Manual BPS V-CO NOTES Nuaire | | nuaire.co.uk 30. 07. 20. Document Number 671760 Western Industrial Estate Caerphilly CF83 1NA...

Table of Contents