APPENDIX F: FEATURE NOTES
When the system is wired for load shedding, the controlled load breaker can remain on the backup loads
panel.
NOTE: The load shedding feature is not applicable to permanently off-grid Powerwall systems. Permanently
off-grid systems use the Backup Gateway Aux terminals for generator control rather than for load shedding.
NOTE: To activate this feature in the Commissioning Wizard, check the Open Relay when Off-Grid box under
"Gateway Low Voltage Relay" on the Installation page. This feature can be activated in firmware version 1.47
or later.
NOTE: See the
Load Shedding with the Backup Gateway application note
for an example installation which
uses the load shedding feature to control a condenser for a central air conditioning system.
NOTE: The low voltage control circuit will be opened briefly during firmware updates and under abnormal
fault conditions.
NOTE: The load shed relay is rated up to 60 V (DC or AC) and 2 A.
Powerwall 2 AC Installation Manual
64