4.4

Connecting Alarms

Depending on the model being installed, the fuse platform will have either of two types of alarm
connectors on the rear side of the platform:
• Screw-down barrier terminal strip
• Wire wrap pin
Figure 16
shows the two types. Connect the connectors as follows:
Screw-down barrier terminal strip: The terminal screw size is 3-48. Terminate wire leads
with crimp-on spade lug or ring connectors that have a maximum width of 0.200 (5.080
mm) or use #16 to #30 AWG copper wire without lugs (insulation stripped back). In
selecting wire size, follow local code referring to the ampacity guidelines provided in
Appendix A of this manual.Tighten the terminal screws to approximately 9 pound-inches
(1 Newton-meter) of force.
Wire-wrap terminal: Wrap terminal block pins using #22 to #26 AWG copper wire with
insulation stripped back. In selecting wire size, follow local code referring to the ampacity
guidelines provided in Appendix A of this manual.
SCREW-DOWN BARRIER TERMINAL STRIP
CONNECT TO CORRESPONDING
ALARM CONNECTORS
CONNECT TO REMOTE ALARMS
CONNECT TO REMOTE ALARMS
CONNECT TO CORRESPONDING
ALARM CONNECTORS
CONNECT TO AUDIO ALARMS
CONNECT TO VISUAL ALARMS
CONNECT TO REMOTE ALARMS
Figure 16. Alarm Contact Connections
WIRE-WRAP PIN TERMINAL BLOCK
ADCP-80-526 • Issue 6 • December 2006
17056-A
Page 21