1 circuit breaker per panel width section in the switchboard
Horizontally oriented: 2 x 50 x 10 mm / vertically oriented: 2 x 50 x 8 mm
1)
2 circuit breakers per panel width section in the switchboard
Horizontally oriented: 2 x 50 x 10 mm / vertically oriented: 2 x 50 x 8 mm
1)
You will find information about the terminals used in Chapter Accessories for connection and
insulation (Page 71).
All other types of connection described (fixed and withdrawable) can be assumed
analogously with the horizontal rear terminals.
Air circuit breaker 3WL10
Manual, 11/2017, L1V30499596002-01
I
Busbar
Com-
u
connection
part-
[A]
[mm]
ment
630
2 x 40 x 5
1
800
2 x 50 x 5
1
1000 2 x 50 x 10 /
1
2 x 50 x 8
1)
1250 2 x 50 x 10 /
1
2 x 50 x 8
1)
I
Busbar
Com-
u
connection
part-
[A]
ment
[mm]
630
2 x 40 x 5
1
2
800
2 x 50 x 5
1
2
1000 2 x 50 x 10 /
1
2 x 50 x 8
2
1)
1250 2 x 50 x 10 /
1
2 x 50 x 8
1)
2
4.1 Types of installation and installation locations
Circuit breaker power with rear terminals for
main circuit connection
Horizontally oriented
Ambient temperature
35 °C
45 °C
55 °C
630 A
630 A
630 A
800 A
800 A
800 A
1000 A
1000 A
1000 A
1250
1250
1200
Circuit breaker power with rear terminals for
main circuit connection
Horizontally oriented
Ambient temperature
35 °C
45 °C
55 °C
630 A
630 A
630 A
630 A
630 A
630 A
800 A
800 A
800 A
800 A
800 A
800 A
1000 A
960 A
920 A
970 A
930 A
900 A
1250
1200
1140
1200
1150
1100
Application planning
Vertically oriented
Ambient temperature
35 °C
45 °C
55 °C
630 A
630 A
630 A
800 A
800 A
800 A
1000
1000
1000
1250
1250
1250
Vertically oriented
Ambient temperature
35 °C
45 °C
55 °C
630 A
630 A
630 A
630 A
630 A
630 A
800 A
800 A
800 A
800 A
800 A
800 A
1000
1000
970
1000
1000
950
1250
1250
1250
1250
1250
1150
115