Removing the Rubber Rings from the Crimping Module
4.5
Use scissors to cut off the joints of the rubber rings to remove them. All rubber rings are removed in
the same way.
(Optional) Installing the Solar Tracker Power Cable
4.6
1. A switch-disconnector-fuse or fuse-switch-disconnector with a voltage of no less than 800 V,
current of 16 A, and protection type of gM needs to be installed between the SUN2000 and the
tracker controller for protection.
2. The cable between the wiring terminal on the power cable and the switch-disconnector-fuse or
fuse-switch-disconnector should be less than or equal to 2.5 meters.
9