5. Data Report

The device will immediately send a version packet report along with an uplink packet including temperature,
humidity and battery voltage.
The device sends data in the default configuration before any configuration is done.
Default setting:
MaxTime : Max Interval = 15 min = 900s
MinTime : Min Interval = 15 min = 900s
BatteryChange: 0x01 (0.1V)
TemperatureChange:0x0064 (1℃)
HumidityChange:0x064 (0.1%)
Note:
The device report interval will be programmed based on the default firmware which may vary.
The interval between two reports must be the minimum time.
Please refer Netvox LoRaWAN Application Command document and Netvox Lora Command Resolver
http://www.netvox.com.cn:8888/page/index
Data report configuration and sending period are as following:
Min Interval
(Unit:second)
Any number between
1~65535
Max Interval
(Unit:second)
Any number between
1~65535
to resolve uplink data.
Reportable Change
Can not be 0.
6
Current Change≥
Reportable Change
Report
per Min Interval
Current Change<
Reportable Change
Report
per Max Interval