Page 1
IMPORTANT! Read and save these instructions. This manual to be left with the equipment. INSTALLATION, OPERATION, AND MAINTENANCE MANUAL Condair DA Series Desiccant Dryer Condair DA-Series Dehumidification...
Page 2
Condair Ltd., except to the extent required for installation, operation or maintenance of the customer's equipment. Liability Notice Condair Ltd. does not accept any liability due to incorrect installation, maintenance or operation of the equipment, or due to the use of parts/components/equipment that are not authorized by Condair Ltd. Copyright Notice Copyright 2020, Condair Ltd., All rights reserved.
Power Supply Requirements Installation 6.5.1 Installing the unit in the room to be dried 6.5.2 Installing the unit in a separate room 6.5.3 Safety 6.5.4 Mounting the Dehumidifier 6.5.5 Connecting the Process Air Duct Condair DA Contents | 3 2593630_A_EN_2003_DA_IOM...
Page 4
Shutting Down the Unit Configuring the Control Software Resetting Alarms Maintenance General Maintenance List Resetting the Service Reminder Troubleshooting 10.1 General Troubleshooting Spare Parts List: Condair DA Commissioning 12.1 General 12.2 First-time Commissioning Decommissioning 13.1 General 13.2 Removing Unit from Service 13.3...
Thank you for purchasing the Condair DA Series Desiccant Dryer. The Condair DA Series Desiccant Dryer incorporates the latest technical advances and meets recognized safety standards. Improper use of the Condair DA Series Desiccant Dryer may result in danger to the user or third parties, and/or damage to property.
Storage, Packaging, and Transportation Storage Store the Condair DA Series Desiccant Dryer in its original packaging inside a protected area that meets the following requirements until it is installed, or if it needs to be stored for an extended period of time: Room temperature: -34 to 104 °F (-30 to 40 °C)
Follow all local guidelines and regulations regarding the installation and operation of the unit; this includes (and not limited to) mounting, plumbing, water, gas, ventilation, and electrical connections. Please consult your local Condair representative to learn more. Condair DA Introduction | 9...
All personnel working with the Condair DA Series Desiccant Dryer unit must be familiar with, and comply with the appropriate regulations on workplace safety and prevention of accidents.
Page 11
The desiccant dryer must NOT be installed in areas where explosion proof equipment is required. Preventing Unsafe Operation All personnel working with the Condair DA Series Desiccant Dryer must immediately report to the customer any secure the unit against accidental power-up...
Controlling humidity in museums and Improving environment in from corrosion archives damp areas "Technical Data" on The Condair DA series comes in seven model sizes with two different voltages. Refer to page 16 for more information. Product Description | 12 Condair DA 2593630_A_EN_2003_DA_IOM...
Circuit Protection Functional Description The Condair DA Series Desiccant Dryer operates with two air streams; a large air stream (process air) and a smaller air stream (reactivation air) that pass through a desiccantin the unit. The air streams pass through the rotor in opposing directions and are driven by fans at the process air inlet and the reactivation air inlet.
Page 14
The operation of the drive system may be observed by opening the front panel of the Condair DA Desiccant Dryer. Note: The rotor will not be damaged even if the fan or the reactivation heater should fail during operation.
Page 15
Electrical Panel The electrical panel is located behind the service panel, in a separate compartment in the dehumidifier. Switches and indications are located on a touch screen on the unit. Condair DA Product Description | 15 2593630_A_EN_2003_DA_IOM...
Product Specifications Technical Data 4.1.1 Capacity Table 1: Condair DA Series Desiccant Dryer Capacities Drying Capacity* Volume Air Regeneration Air Moisture Removed Condair DA Voltage Moved Volume Unit V Ph Hz lbs/h /min (m /min (m (kg/h) Condair DA 300 294 (499.5)
4.1.3 Dimensions Table 3: Condair DA Dimensions Air Connection Diameters Casing Dimensions Rotor Size Depth x Width in (mm) Diameter x Thickness x Height Proc- React- in (mm) in (mm) ivation Condair DA 300 Condair DA 400 17.7 x 5.5 (450 x 140)
Power Consumption and Loads: Condair DA Condair DA Condair DA Condair DA Condair DA Condair DA Condair DA 1400 2000 2400 Drying 11.2 15.6 22.0 29.7 31.9 44.1 Capacity (3.3) (5.1) (7.1) (10.0) (13.5) (14.5) (20.0) lbs/h (kg/h) Voltage 208 V...
4.2.5 Other Maximum Noise Level at distance = 1 m (3 ft) , with applied ducting Condair Condair Condair Condair Condair Condair DA Condair DA 300 DA 400 DA 600 DA 800 DA 1400 2000 DA 2400 Noise Level dB...
A. Process air inlet: Ø 15.7 in (400 mm) B. Dry air outlet: Ø 12.4 in (315 mm) C. Reactivation air inlet: Ø 7.9 in (200 mm) D. Wet air outlet: Ø 7.9 in (200 mm) Specification Drawings | 20 Condair DA 2593630_A_EN_2003_DA_IOM...
Observe and comply with all local and national codes dealing with electrical installations. Condair does not accept any liability for installation of humidification or dehumidification equipment by unqualified personnel, or the use of equipment and parts that are not authorized by Condair. Personnel Qualifications All installation work must be performed only by licensed personnel authorized by the customer.
The Condair DA Desiccant Dryer is designed for indoor installation and can be installed, with ducts, in the room to be dehumidified or in a separate room. The installation requires a duct to remove wet air from the Condair DA Desiccant Dryer, an air duct for the reactivation air, a duct for the dry air outlet (recommended, especially for distribution), and connection to the mains supply (with disconnect switch).
Electrical disconnect switch Installation The Condair DA Desiccant Dryer may be installed in the dehumidified room, or in a separate room. To obtain the best performance, equip diffuser to fan outlets. IMPORTANT! Ensure that the rooms supplying air to the dehumidifier and rooms requiring dry air from the dehumidifier are properly vented to reduce formation of pressure imbalance.
Does not require duct if coming from the room housing the unit. Requires a duct if coming from elsewhere. Wet air leaves the unit to another location or outside. Requires duct out of the room housing the unit. 24 | Installation and Planning Condair DA 2593630_A_EN_2003_DA_IOM...
"Mounting Requirements" Refer to for mounting requirements. The Condair DA Desiccant Dryer comes equipped with legs and is intended to be mounted indoors and on the floor. It is recommended to bolt the legs down to the floor. Mounting considerations: Ensure that there is enough clearance around the unit for ducting and servicing.
Connecting the Process Air Duct Typical installations of the Condair DA Desiccant Dryer do not require a process air duct to the unit because the unit is installed in the space needing dehumidification. Instead, air into the dehumidifier is taken from the space directly.
~0.15-0.25 in (4-6mm) may be drilled at the duct's lowest position. Alternatively, a drain line may installed in the duct. Contact your Condair representative for information on proper draining. Place warning signs at the outlet, or where applicable. The wet air temperature may reach above 176 °F (80 °C).
□ Power supply meet the voltage and current requirements shown on the specification label? Refer to "Model Designation" on page 13. □ All cables fastened securely? □ All electrical connections meet applicable codes? □ Electrical installation meet the applicable national and local codes? 28 | Installation and Planning Condair DA 2593630_A_EN_2003_DA_IOM...
User Interface Control Software The programmable logic controller (PLC) in the Condair DA Desiccant Dryer features a touchscreen, LCD display, that allows you to control the dehumidifier, runtime meters, and alarms. The controller also features functions to protect the rotor from excess rotation, functions to safely cool the internal heater, and functions that control dehumidity through an external 0-10 V humidity sensor or control signal.
5 V, the second heating is activated (if applicable. The reactivation fan runs at full speed. 7.1.4 I/O Input Outputs Page The I/O's page shows the current digital inputs and outputs in the controller. 30 | User Interface Condair DA 2593630_A_EN_2003_DA_IOM...
Modbus, TCP/IP, or remotely. See "Communication Settings" on page 35 7.1.5.1 Runtime The Runtime page shows the active time of components in the Condair DA Desiccant Dryer, as well as the total dehumidifier runtime, and hours since maintenance. Condair DA User Interface | 31...
To remove the alarm (after resolving the issue), the alarm must first be acknowledged . This is done by accessing the Pending Alarms page and viewing the alarm's details. 32 | User Interface Condair DA 2593630_A_EN_2003_DA_IOM...
Page 33
Alarm Details page, where you press acknowledge the alarm. Reset Pressing will reset the alarm, only if the cause for the alarm is NOT active. IMPORTANT! Reset an alarm after it has been acknowledged. Condair DA User Interface | 33 2593630_A_EN_2003_DA_IOM...
Clear alarm history 7.1.5.3 Service Level Settings Password: 1111 There are two service level pages. The second service level page is accessed by pressing the arrow button at the bottom of the screen. 34 | User Interface Condair DA 2593630_A_EN_2003_DA_IOM...
- displays the dehumidication demand between 0-100 (stop = 0, start = 30). IMPORTANT! The PID settings should not be changed. Consult your Condair representative. In addition to this, the second service level page shows buttons that will allow you to clear the alarm history (refer "Resetting Alarms"...
Operation General Personnel Qualifications The Condair DA Series Desiccant Dryer must only be operated by personnel who are adequately qualified, competent, and are authorized by the customer. Safety Observe the following safety precautions. DANGER! Risk of electric shock! The unit is mains powered. Using the On/Off button on the touch screen to shut down the unit will not remove power from the unit.
The desiccant dryer must NOT be installed in areas where explosion proof equipment is required. Starting Up Ensure that the proper commissioning has been performed, and the Condair DA Desiccant Dryer is connected to "First-time Commissioning" on page 46 the mains power supply. Refer to To start the Condair DA Desiccant Dryer: 1.
Analog Setpoint - humidity setpt for hum sensor On/Off (see shutting down/starting) Turn on cooling fan Set unit to automatic or manual Allow process fan to run continuously Resetting Alarms "Reset Alarms" on page 41 Refer to 38 | Operation Condair DA 2593630_A_EN_2003_DA_IOM...
Incorrect service and maintenance may reduce the efficiency of the unit. Perform the following maintenance tasks at the (suggested) intervals specified in Table 5 on the next page . For "Spare Parts List: Condair DA" on page 44 the components referenced in the table, refer to Condair DA Maintenance | 39...
The threshold values for runtime hours may be changed, but "Service only after consulting your Condair representative. For more information about runtime hours, refer to Level Settings" on page 34 To reset runtime hours:...
Page 41
To acknowledge an alarm: Menu Alarms Pending Alarms page > > > Details > Details > Reset To reset an alarm, tap on the button when viewing your pending alarms. Condair DA Maintenance | 41 2593630_A_EN_2003_DA_IOM...
Electrical repairs must only be performed by a licensed electrician authorized by the customer, or by Condair service technicians. Troubleshooting the Condair DA Series Desiccant Dryer may require the user to access the inside of the unit, to the control cabinets, which may expose the user and equipment to hazards described in "For Your Safety"...
Page 43
Check the rotor shaft and rotor rim for blockages or damage. Check the drive belt for wear and proper tension, 15° deflection. Electrical heater is faulty, or the reactivation temperature has been changed. Check the reactivation heater and check the fuses. Condair DA Troubleshooting | 43 2593630_A_EN_2003_DA_IOM...
Spare Parts List: Condair DA For ordering, contact Condair. 45, 50, 55 5 + 10 Figure 6 - Spare Parts. Refer to Table 6 on the next page Condair DA Spare Parts List: Condair DA | 44 2593630_A_EN_2003_DA_IOM...
Page 45
Cabinet Seals (roll) Over-temperature Mounting Components Over-temperature probe and switch Heat Shield, Reactivation Process Air Fan Reactivation Air Fan Process Air Filter Reactivation Air Filter Spare Hardware N/S = item not shown Condair DA Spare Parts List: Condair DA | 45 2593630_A_EN_2003_DA_IOM...
12.1 General The Condair DA Series Desiccant Dryer must be commissioned and operated only by personnel who are adequately qualified and familiar with the Condair DA Series Desiccant Dryer. It is the customer's responsibility to verify the qualifications of personnel.
Decommissioning 13.1 General If the Condair DA Series Desiccant Dryer needs to be replaced or removed from service for disposal, strictly follow the instructions in this section. Personnel Qualifications All decommissioning work must be performed only by a qualified service technician authorized by the customer.
Page 48
APPENDIX Condair DA Appendix 2593630_A_EN_2003_DA_IOM...
Page 49
□ Power supply meet the voltage and current requirements shown on the specification label? Refer to "Model Designation" on page 13. □ All cables fastened securely? □ All electrical connections meet applicable codes? □ Electrical installation meet the applicable national and local codes? Condair DA Installation Checklist | 49 2593630_A_EN_2003_DA_IOM...
Page 50
B Appendix: Maintenance Checklist Condair DA Maintenance Checklist | 50 2593630_A_EN_2003_DA_IOM...
Page 51
Table 7: Maintenance Log...continued Component Frequency Dates Last Performed (DD/MM/YY) and Initials Comments: Condair DA Maintenance Checklist | 51 2593630_A_EN_2003_DA_IOM...
Page 53
D Appendix: Communication Modbus The Condair DA Desiccant Dryer supports Modbus RTU with RS 232 interfaces. Support for Modbus RS485 and TCP/IP can be added with an optional communication card. Table 8: RS 232 Pin Interfaces Pin # RS 232 (Port 1) Not connected Signals are related to the controller’s 0V;...
Page 54
React. Heater step 1 16385 1=On Process air fan 16386 1=On React. Air fan 16387 1=On Drive motor 16388 1=On Alarm indication 16389 1=On React. Heater step 2 16391 1=On React. Heater step 3 54 | Communication Condair DA 2593630_A_EN_2003_DA_IOM...
Page 57
Warranty Condair Inc. and/or Condair Ltd. (hereinafter collectively referred to as THE COMPANY), warrant for a period of two years after installation or 30 months from manufacturer’s ship date, whichever date is earlier, that THE COMPANY’s manufactured and assembled products, not otherwise expressly warranted, are free from defects in material and workmanship.
Page 58
CONSULTING, SALES, AND SERVICE: CANADA 2740 Fenton Road Ottawa, ON, K1T 3T7 Tel: 1.866.667.8321 Fax: 613.822.7964 na.info@condair.com www.condair.com...