Fuse Carriage; Introduction; Description - Siemens RL Series Instructions Manual

Low voltage circuit breakers
Hide thumbs Also See for RL Series:
Table of Contents

Advertisement

Fuse Carriage

Introduction

Type RFC-3200 through RFC-5000 fuse carriages for use
with Type RLF-3200 through RLF-5000 circuit breakers are
furnished for mounting in metal-enclosed switchgear of the
1 2
Drawout type. (See Fi g u res
completely assembled, tested, and calibrated at the factory in
a
vertical position, and must be so installed to operate
properly.

Description

The basic RL-3200, RL-4000 and RL-5000 unfused circuit
breakers have continuous current ratings equal to their frame
size (3200A, 4000A or 5000A) or tripping transformer rating
(whichever is lower), and interrupting ratings as shown in the
descriptive bulletin.
When used i n conjunction with the separately mounted type
RFC fuse carriage, the circuit breaker designations become
RLF-3200, RLF-4000 and
RLF-5000. The fused breakers
have an attachment that operates to open the circuit breaker
when one or more of the current limiting fuses opens. The
interruption rating of the combination of fuses and circuit
breaker is increased to the interrupting rating of the fuses -
200,000 amperes symmetrical at 600 volts or less.
The continuous current rating may be restricted by the fuse
When
size used .
equipped with 6000 amperes fuses, the
RLF-5000 combination is rated at 5000 amperes continuous.
RLF-4000 combination is rated a t 4000 amperes continuous
combination
The
RLF-3200
continuous when eq uipped with 5000-ampere fuses. The
circuit breaker continuous ratings are reduced when smaller
rated fuses are used. (Refer to the catalog for application
information.)
The type RFC fuse carriages are p rovided with open-fuse
sensors connected to the open-fuse trip attachment, which is
mou nted on the circuit breaker. This device opens the circuit
more
breaker when one or
of the current-limiting fuses ope n .
Note:
Tripping depends on voltage b e i n g developed across
the
the open fuse by
power source. NO TRIPPING
OCCUR I F THE POWER C I RC U I T I S DE-ENERGIZED.
and 1 3 ). All fuse carriages are
is
rated
at
3200
amperes
WILL
·
F i g u re
1 2.Fuse Carriage Compartment with
F i g u re 1 3 .
Fuse Carriage in Compartment with
Door
Closed
Door
Open