Viessmann VITODENS 200-W Installation And Service Instructions For Contractors page 70

1.9 to 32 kw, wall mounted gas condensing boiler with 7 inch colour touchscreen, natural gas and lpg version
Table of Contents

Advertisement

System configuration (parameters)
DHW
(cont.)
1085.0 "Cylinder heating: Set start point"
Setting
1087.0 "Max. duration, DHW heating"
Setting
1087.1 "Min. delay until next DHW heating"
Setting
1101.2 "Set speed of the primary circuit pump for DHW heating"
Setting
70
Explanations
Start point for DHW heating below set DHW tempera-
ture
25
Delivered condition start point 2.5 K below set DHW
temperature
10 to 100
Adjustable start points:
10:
1.0 K ...
100: 10.0 K
Irrespective of this, the stop point is 2.5 K above the
set DHW temperature.
Explanations
After a set period of time has elapsed, DHW heating
ends even though the set DHW temperature has not
yet been reached.
Not adjustable on gas condensing combi boilers
60
Factory setting 60 min
0
No time limit for DHW heating
1 to 240
Duration of DHW heating adjustable from 1 to 240 min
in 1 min increments
Explanations
Minimum delay before DHW heating starts again,
even though there is a demand.
Cannot be adjusted on gas condensing combi boilers
60
Delivered condition, delay of 60 min
60 to 240
Delay adjustable from 60 to 240 min in 1 min incre-
ments
Explanations
Set speed of the internal circulation pump when oper-
ated as a circulation pump for cylinder heating
...
Delivered condition specified by settings specific to
the appliance
20 to 100
Set speed adjustable from 20 to 100 %