DHW
(cont.)
497.2 "DHW circulation pump for DHW heating"
Setting
Off
On
497.3 "Number of cycles DHW circulation pump"
Setting
503.0 "Scald protection"
Setting
OFF
ON
534.0 "Circulation pump run-on"
Setting
120 s
Explanations
DHW circulation pump:
0
Switched off during DHW heating
1
ON during DHW heating to standard set value
Explanations
Number of cycles per hour for 5 minutes each during
the selected time phase:
0
1 cycle
1
2 cycles
2
3 cycles
3
4 cycles
4
5 cycles
5
6 cycles
Explanations
The adjustable water temperature is limited to a maxi-
mum value.
0
Scald protection OFF
Danger
Risk of injury due to increased DHW tempera-
ture.
Inform the system user of the risk from the high-
er outlet temperature at the taps.
1
Scald protection ON (maximum DHW temperature 60
°C)
Note
Even with the scald protection switched on, higher
outlet temperatures may occur at the draw-off points
in the following cases:
With active hygiene function
While the appliance is being calibrated
Explanations
Circulation pump run-on after cylinder heating
120
Delivered condition 120 s run-on
0 to 900
Run-on time adjustable from 0 to 900 s in 60 s incre-
ments (the run-on time is rounded down to full mi-
nutes)
Note
To avoid damaging the appliance, do not set the run-
on time to < 120 s.
System configuration (parameters)
69