2. Select the Best Location

Select space for installation outside unit, which will meet the following conditions.
With strength which bears weight of unit
With space for air passage and service work
Don't install the unit at the space where generation, inflow, stagnation, and leak of combustible gas is expected.
Avoid unit installation in a place where acidic solution and spray (sulfur) are often used.
Location with no leakage of combustible gas
Recommend the outside unit to be installed within 0~40°C.
Location with installation or service work space (Refer to required space)
Do not use the outside unit under any special environment where oil, steam and sulfuric gas exist.
Install in a separate machine room not exposed to external air
– Establish an anti-freeze plan for the water supply when the product is stopped during the winter.
– Install the product so that the noise from the machine room is not transferred outsides
The floor of the machine room must be water proof.
Drainage must be installed in the machine room to process the water drainage.
Install a floor slope to make the drainage smooth.
Avoid installing the outside unit in the location with following conditions.
Location where corrosive gas such as acidic gas is generated. (It may cause the refrigerant leakage by corrosion
of the pipe.)
Location where electromagnetic waves happen. (It may cause the abnormal operation by control parts disorder.)
Location to be able to leak the combustible gas
Location with carbon fiber or combustible dust.
Location with the combustible material like thinner or gasoline. (It may cause a fire by leaking the gas near the
product.)
CAUTION
1. Do not install Multi V water outside. Always install ventilated indoors.
2. Inverter product may generate electric noise. Keep the body from computer, stereo etc. at enough
distance. Specially leave space from indoor remote controller to shoes electric devices at the above 3m
in weak electric wave area. Insert the power cable and other wire into separate conduit.
Heat Pump