Download Print this page

Honeywell WEB-O3022H Product Data page 4

Ciper expansion i/o modules
Hide thumbs Also See for WEB-O3022H:

Advertisement

CIPer MODEL 30 EXP I/O MODULES - PRODUCT DATA
Safety Information as per EN60730-1
The Open System is intended for residential, commercial,
and light-industrial environments. The Open System is an
independently mounted electronic control system with
fixed wiring.
The WEB-O9056H and WEB-O3022H are suitable for
mounting in fuse boxes conforming with standard
DIN43880 and having a slot height of max. 1.77 inches
(45 mm).
It is suitable for panel rail mounting on 1.38 inches (35
mm) standard panel rail (both horizontal and vertical rail
mounting possible).
Table 3. Safety information as per EN-60730-1
Electric Shock
PELV
Protection
Pollution Degree 2, suitable for use in
Pollution Degree
industrial environments.
Installation
Class 3
Overvoltage
24 V-powered controls: Category I
Category
Rated Impulse
330 VAC for Category I (SELV)
Voltage
Automatic
Type 1
Action
Software Class
Class A
Operating Control, Open Energy
Purpose of control
Management Equipment.
Enclosure degree
IP20 (NEMA 1)
of protection
>75 °C for all housing and plastic
Ball-pressure
parts.
Test
>125 °C in the case of devices
Temperature
applied with voltage-carrying
parts, connectors, and terminals.
Electromagnetic
Tested at 230 VAC with the
Interference
modules in normal condition.
Europe: safety isolating
transformers according to
System
IEC61558-2-6.
Transformer
U.S.A. and Canada: NEC Class-2
transformers.
Honeywell Building Technologies
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
customer.honeywell.com
Mounting
The CIPer Model30 expansion I/O modules can be
mounted in any orientation on a DIN rail. Ventilation
openings are designed into the cover to allow proper
heat dissipation, regardless of mounting orientation.
When mounting on DIN rail, the locking clip present
on both I/O modules ensures accurate alignment of
connectors between all modules.
The controller can also be screw-mounted on a panel
using the four mounting tabs, accessible under the
covers. These mounting tabs may be broken off if
needed to save space when DIN rail mounting.
Note:
Avoid mounting in areas where acid fumes or
o
other deteriorating vapors can attack the metal
parts of the controller, or in areas where
escaping gas or other explosive vapors are
present.
Mount in a position that allows clearance for
o
wiring, servicing and removal.
For complete mounting and wiring information,
o
refer to the CIPer Model 30 expansion I/O
Installation Instructions.
© 2019 Honeywell International Inc.
31-00239EFS| Rev. 01 10-19

Advertisement

loading

This manual is also suitable for:

Web-o9056h