Specifications
Electrical
Rated input voltage: 20-30 VAC; 50/60Hz Power
consumption:
WEB-O9056H:
207VA maximum for I/O module with all
o
oads.
connected l
35 VA maximum for I/O module without any
o
load.
WEB-O3022H:
87VA maximum for I/O module with all
o
oads.
connected l
15 VA maximum for I/O module without any
o
load.
Operating Environment
Ambient temperature: -4 to 131
Storage temperature: -4 to 150
Humidity: 5% to 95% non-condensing
Inputs and Outputs
Analog Outputs (AO)
AOs are individually configurable for current or
voltage. Universal Inputs marked as UI-x/AO-x are
configurable as AOs.
Analog Current Outputs
Current Output Range: 4.0 to 20.0 mA
Output Load Resistance: 550 Ohms maximum
Analog Voltage Outputs
Voltage Output Range: 0.0 to 10.0 VDC Maximum
Output Current: 10.0 mA
Digital Outputs (DO)
Voltage rating: 20 to 30 VAC @ 50/60Hz
Digital Outputs type: Solid-State Relay
Current rating: 1.5A Continuous, 3.5A in-rush for
100 milliseconds
Universal Inputs (UI)
Flexible UI's to connect external sensors like 20KNTC,
PT1000 and other resistive sensors.
Pulse Inputs:
Type: Dry contact
Frequency: 100Hz max,
Duty cycle: minimum 5 ms ON / 5 ms OFF
F (-20 to 55
C)
°
°
F (-20 to 65
C)
°
°
3
CIPer MODEL 30 EXP I/O MODULES - PRODUCT DATA
Table 2. Universal Inputs specifications
Input Type
Sensor Type
Room/Zone
Discharge Air
20K Ohm NTC
Outdoor Air
Temperature
C7031G
Outdoor Air
C7041F
Temperature
PT1000
(IEC751
3850)
TR23
500 Ohm to
Setpoint
10,500 Ohm
Potentiometer
Resistive Input
Generic
Transducer,
Voltage Input
Controller
Dry Contact
Discrete Input
closure
Status Indication LEDs
The expansion I/O modules indicate the device Power
and Fault status using the LEDs on top.
Standards and Approvals
UL/CUL (E87741) listed under UL 60730-1 and CSA
E60730-1, UL 60730-2-9:2010.
Meets FCC Part 15, Subpart B:2017, Class B (radiated
emissions) requirements.
Meets Canada ICES-003:2016.
EMC Directive: 2014/30/EU. Standards Applied:
EN 61000-6:2005
o
EN 61000-6-3:2007 + A1
o
EN 60730-1: 2011, EN 60730-2-9: 2010
o
RoHS Directive: 2011/65/EU.
Standard EN 50581: 2012
o
Conformance Statement
This digital apparatus complies with CAN ICES-3 (B)/
NMB-3 (B).
FCC Notice
This device complies with Part 15 of the FCC rules.
Operation is subject to the following two conditions:
(1) this device may not cause harmful interference,
(2) this device must accept any interference received,
including interference that may cause undesired
operation.
Operating Range
-40° F to 199° F
(-40° C to 93° C)
-40° F to 120° F
(-40° C to 49° C)
-40° F to 250° F
(-40° C to 121° C)
-40° F to 199° F
(-40° C to 93° C)
50° F to 90° F
(10° C to 32° C)
100 Ohms to 100K
Ohms
0 - 10 VDC
OpenCircuit ≥ 3000
Ohms
ClosedCircuit < 3000
Ohms
31-00239EFS-01